NERC Reliability Standard definition

NERC Reliability Standard means a FERC approved requirement, whether now existing or hereafter amended, modified or supplemented from time to time, to provide for reliable operation of the bulk power system, including without limiting the foregoing, requirements for the operation of existing bulk power system facilities, including cyber security protection, and including the design of planned additions or modifications to such facilities to the extent necessary for reliable operation of the bulk power system; but shall not include any requirement to enlarge bulk power system facilities or to construct new transmission capacity or generation capacity.

Examples of NERC Reliability Standard in a sentence

  • The Customer Facility shall be designed to remain in service (not trip) for frequencies and times as specified in Attachment 2 of NERC Reliability Standard PRC-024-1, and successor Reliability Standards, for both high and low frequency condition, irrespective of generator size, subject to the permissive trip exceptions established in PRC-024-1 (and successor Reliability Standards).

  • Generation Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard that provides for equivalent or more stringent parameters.

  • Generation Interconnection Customer is required to install a governor or equivalent controls with the capability of operating: (1) with a maximum 5 percent droop and ±0.036 Hz deadband; or (2) in accordance with the relevant droop, deadband, and timely and sustained response settings from an approved NERC Reliability Standard providing for equivalent or more stringent parameters.

  • The droop characteristic shall be: (1) based on the nameplate capacity of the Customer Facility, and shall be linear in the range of frequencies between 59 to 61 Hz that are outside of the deadband parameter; or (2) based an approved NERC Reliability Standard providing for an equivalent or more stringent parameter.

  • Interconnection Customer is required to install a governor or equivalent controls with the capability of operating: (1) with a maximum 5 percent droop and ±0.036 Hz deadband; or (2) in accordance with the relevant droop, deadband, and timely and sustained response settings from an approved NERC Reliability Standard providing for equivalent or more stringent parameters.

  • Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (a) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (b) implement the relevant droop and deadband settings from an approved NERC Reliability Standard that provides for equivalent or more stringent parameters.

  • Interconnection Customer shall: (1) in coordination with Transmission Provider and/or the relevant balancing authority, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard that provides for equivalent or more stringent parameters.

  • Interconnection Customer shall: (1) in coordination with System Operator and Interconnecting Transmission Owner, set the deadband parameter to: (1) a maximum of ±0.036 Hz and set the droop parameter to a maximum of 5 percent; or (2) implement the relevant droop and deadband settings from an approved NERC Reliability Standard that provides for equivalent or more stringent parameters.

  • The droop characteristic shall be: (1) based on the nameplate capacity of the Generating Facility, and shall be linear in the range of frequencies between 59 to 61 Hz that are outside of the deadband parameter; or (2) based an approved NERC Reliability Standard providing for an equivalent or more stringent parameter.

  • Generation Project Developer is required to install a governor or equivalent controls with the capability of operating: (1) with a maximum 5% droop and ±0.036 Hz deadband; or (2) in accordance with the relevant droop, deadband, and timely and sustained response settings from an approved NERC Reliability Standard providing for equivalent or more stringent parameters.

Related to NERC Reliability Standard

  • NERC Reliability Standards means the most recent version of those reliability standards applicable to the Generating Facility, or to the Generator Owner or the Generator Operator with respect to the Generating Facility, that are adopted by the NERC and approved by the applicable regulatory authorities, which are available at ▇▇▇▇://▇▇▇.▇▇▇▇.▇▇▇/files/Reliability_Standards_Complete_Set.pdf, or any successor thereto.

  • Reliability Standard means a requirement to provide for reliable operation of the bulk power system, including without limiting the foregoing requirements for the operation of existing bulk power system facilities, including cybersecurity protection, and the design of planned additions or modifications to such facilities to the extent necessary for reliable operation of the bulk power system, but shall not include any requirement to enlarge bulk power system facilities or to construct new transmission capacity or generation capacity.

  • Reliability Standards means the criteria, standards, rules and requirements relating to reliability established by a Standards Authority.

  • NYSRC Reliability Rules means the rules applicable to the operation of the New York Transmission System. These rules are based on Reliability Standards adopted by NERC and NPCC, but also include more specific and more stringent rules to reflect the particular requirements of the New York Transmission System.

  • Service Level Standards has the meaning ascribed thereto in Section 2.1 hereof.