Asynchronous Generating definition

Asynchronous Generating. Facility shall mean an induction, doubly-fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current. Balancing Authority shall mean the responsible entity that integrates resource plans ahead of time, maintains load-interchange-generation balance within a Balancing Authority Area, and supports Interconnection frequency in real time. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load-resource balance within this area. Base Case shall mean the base case power flow, short circuit, and stability data bases used for the Interconnection Studies. Breach shall mean the failure of a Party to perform or observe any material term or condition of this LGIA. Breaching Party shall mean a Party that is in Breach of this LGIA. Business Day shall mean Monday through Friday, excluding federal holidays and the day after Thanksgiving Day.
Asynchronous Generating. Facility shall mean an induction, doubly-fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current Balancing Authority shall mean the responsible entity that integrates resource plans ahead of time, maintains load-interchange-generation balance within a Balancing Authority Area, and supports Interconnection frequency in real time. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load-resource balance within this area. Base Case shall mean the base case power flow, short circuit, and stability data bases used for the Interconnection Studies. Breach shall mean the failure of a Party to perform or observe any material term or condition of this LGIA. Breaching Party shall mean a Party that is in Breach of this LGIA. Business Day shall mean Monday through Friday, excluding federal holidays and the day after Thanksgiving Day. CAISO Controlled Grid shall mean the system of transmission lines and associated facilities of the parties to the Transmission Control Agreement that have been placed under the CAISO’s Operational Control. CAISO Tariff shall mean the CAISO’s tariff, as filed with FERC, and as amended or supplemented from time to time, or any successor tariff. Calendar Day shall mean any day including Saturday, Sunday or a federal holiday. Commercial Operation shall mean the status of an Electric Generating Unit or project phase at a Generating Facility that has commenced generating electricity for sale, excluding electricity generated during Trial Operation. Commercial Operation Date of an Electric Generating Unit or project phase shall mean the date on which the Electric Generating Unit or project phase at the Generating Facility commences Commercial Operation as agreed to by the applicable Participating TO, the CAISO, and the Interconnection Customer pursuant to Appendix E to this LGIA, and in accordance with the implementation plan agreed to by the Participating TO and the CAISO for multiple individual Electric Generating Units or project phases at a Generating Facility where an Interconnection Customer intends to establish separate Commercial Operation Dates for those Electric Generating Units or project phases. Confidential Information shall mean any confidential, proprietary or trade secret information of a plan, specification, pattern, procedure, design, device, list, concept, policy ...
Asynchronous Generating. Facility shall mean an induction, doubly-fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current. Balancing Authority shall mean the responsible entity that integrates resource plans ahead of time, maintains load-interchange-generation balance within a Balancing Authority Area, and supports Interconnection frequency in real time. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load-resource balance within this area. Base Case shall mean the base case power flow, short circuit, and stability data bases used for the Interconnection Studies. Breach shall mean the failure of a Party to perform or observe any material term or condition of this LGIA. Breaching Party shall mean a Party that is in Breach of this LGIA. Business Day shall mean Monday through Friday, excluding federal holidays and the day after Thanksgiving Day. Calendar Day shall mean any day including Saturday, Sunday or a federal holiday. Commercial Operation shall mean the status of an Electric Generating Unit at a Generating Facility that has commenced generating electricity for sale, excluding electricity generated during Trial Operation. Commercial Operation Date of an Electric Generating Unit shall mean the date on which the Electric Generating Unit at the Generating Facility commences Commercial Operation as agreed to by the applicable Participating TO and the Interconnection Customer pursuant to Appendix E to this LGIA. Confidential Information shall mean any confidential, proprietary or trade secret information of a plan, specification, pattern, procedure, design, device, list, concept, policy or compilation relating to the present or planned business of a Party, which is designated as confidential by the Party supplying the information, whether conveyed orally, electronically, in writing, through inspection, or otherwise, subject to Article 22.1.2. Default shall mean the failure of a Breaching Party to cure its Breach in accordance with Article 17 of this LGIA. Distribution System shall mean those non-CAISO-controlled transmission and distribution facilities owned by the Participating TO. Distribution Upgrades shall mean the additions, modifications, and upgrades to the Participating TO’s Distribution System. Distribution Upgrades do not include Interconnection Facilities. Effective Date shall mean the date on which thi...

Examples of Asynchronous Generating in a sentence

  • For all Generating Facilities other than Asynchronous Generating Facilities, the Interconnection Customer shall design the Large Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of the Electric Generating Unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO has established different requirements that apply to all generators in the Balancing Authority Area on a comparable basis.

  • The Interconnection Customer shall not disable power factor equipment while the Asynchronous Generating Facility is in operation.

  • Asynchronous Generating Facilities shall also be able to provide sufficient dynamic voltage support in lieu of the power system stabilizer and automatic voltage regulation at the generator excitation system if the Phase II Interconnection Study shows this to be required for system safety or reliability.

  • The requirements of this Article 5.4 shall apply to Asynchronous Generating Facilities in accordance with Appendix H.

  • An Asynchronous Generating Facility shall comply with the off nominal frequency requirements set forth in the WECC Under Frequency Load Shedding Relay Application Guide or successor requirements as they may be amended from time to time.

  • Asynchronous Generating Facilities shall be subject to frequency ride through capability requirements in accordance with Appendix H to this LGIA.

  • For Asynchronous Generating Facilities, the Interconnection Customer shall design the Large Generating Facility to maintain power factor criteria in accordance with Appendix H of this LGIA.

  • An Asynchronous Generating Facility shall operate within a power factor within the range of 0.95 leading to 0.95 lagging, measured at the Point of Interconnection as defined in this LGIA in order to maintain a specified voltage schedule, if the Phase II Interconnection Study shows that such a requirement is necessary to ensure safety or reliability.

  • Asynchronous Generating Facilities may be tripped after the fault period if this action is intended as part of a special protection system.

  • Clearing time shall be based on the maximum normal clearing time associated with any three-phase fault location that reduces the voltage at the Asynchronous Generating Facility’s Point of Interconnection to 0.2 per-unit of nominal voltage or less, independent of any fault current contribution from the Asynchronous Generating Facility.


More Definitions of Asynchronous Generating

Asynchronous Generating. Facility shall mean an induction, doubly-fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current. Balancing Authority shall mean the responsible entity that integrates resource plans ahead of time, maintains load-interchange-generation balance within a Balancing Authority Area, and supports Interconnection frequency in real time. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load- resource balance within this area. Breach shall mean the failure of a Party to perform or observe any material term or condition of this LGIA. Breaching Party shall mean a Party that is in Breach of this LGIA. Business Day shall mean Monday through Friday, excluding federal holidays and the day after Thanksgiving Day. CAISO Controlled Grid shall mean the system of transmission lines and associated facilities of the parties to the Transmission Control Agreement that have been placed under the CAISO’s Operational Control. CAISO Tariff shall mean the CAISO’s tariff, as filed with FERC, and as amended or supplemented from time to time, or any successor tariff. Calendar Day shall mean any day including Saturday, Sunday or a federal holiday. Commercial Operation shall mean the status of an Electric Generating Unit or project phase at a Generating Facility that has commenced generating electricity for sale, excluding electricity generated during Trial Operation. Commercial Operation Date of an Electric Generating Unit or project phase shall mean the date on which the Electric Generating Unit or project phase at the Generating Facility commences Commercial Operation as agreed to by the applicable Participating TO, the CAISO, and the Interconnection Customer pursuant to Appendix E to this LGIA, and in accordance with the implementation plan agreed to by the Participating TO and the CAISO for multiple individual Electric Generating Units or project phases at a Generating Facility where an Interconnection Customer intends to establish separate Commercial Operation Dates for those Electric Generating Units or project phases.
Asynchronous Generating. Facility shall mean an induction, doubly- fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load- resource balance within this area. Balancing Authority Area Service shall mean a service provided by a Balancing Authority to maintain reliability and/or comply with Applicable Reliability Standards. Base Case shall include, among other things, base case power flow, short circuit, and stability data bases used for Interconnection Studies by IID.
Asynchronous Generating. Facility shall mean an induction, doubly-fed, or electronic power generating unit(s) that produces 60 Hz (nominal) alternating current. Balancing Authority shall mean the responsible entity that integrates resource plans ahead of time, maintains load-interchange-generation balance within a Balancing Authority Area, and supports Interconnection frequency in real time. Balancing Authority Area shall mean the collection of generation, transmission, and loads within the metered boundaries of the Balancing Authority. The Balancing Authority maintains load-resource balance within this area. Base Case shall mean the base case power flow, short circuit, and stability data bases used for the Interconnection Studies. Base Case shall mean data including, but not limited to, base case power flow, short circuit, and stability data bases, underlying load, generation, and transmission facility assumptions, contingency lists, including relevant special protection systems, and transmission diagrams used to perform Phase I Interconnection and Phase II Interconnection Studies. The Base Case may include Critical Energy Infrastructure Information (as that term is defined by FERC). The Base Case shall include transmission facilities as approved by the Distribution Provider or ISO, as applicable, and Distribution Upgrades and Network Upgrades associated with generating facilities in (iv) below and generating facilities that (i) are directly interconnected to the Distribution System or ISO Grid; (ii) are interconnected to Affected Systems and may have an impact on the Interconnection Request; (iii) have a pending request to interconnect to the Distribution System or an Affected System; or (iv) are not interconnected to the Distribution System or ISO Grid, but are subject to a fully executed generator interconnection agreement (or its equivalent predecessor agreement) or for which an unexecuted generator interconnection agreement (or its equivalent predecessor agreement) has been requested to be filed with FERC. Breach shall mean the failure of a Party to perform or observe any material term or condition of this LGIAthe GIA. Breaching Party shall mean a Party that is in Breach of this LGIAthe GIA. Business Day shall mean Monday through Friday, excluding federal holidays and the day after Thanksgiving DayFederal Holidays.

Related to Asynchronous Generating

  • Electric generation service means the provision of retail

  • Asynchronous means not simultaneous or concurrent in time. For the purpose of this general rule, asynchronous telecommunication technologies for telemedicine or telehealth services may include audio and video, audio without video, client or member portal and may include remote monitoring. "Asynchronous" does not include voice messages, facsimile, electronic mail or text messages.¶

  • Electric generating unit means an individual electric generator and its associated plant and apparatus whose electrical output is capable of being separately identified and metered. Emergency Condition shall mean a condition or situation: (1) that in the judgment of the Party making the claim is imminently likely to endanger life or property; or (2) that, in the case of the CAISO, is imminently likely (as determined in a non-discriminatory manner) to cause a material adverse effect on the security of, or damage to, the CAISO Controlled Grid or the electric systems of others to which the CAISO Controlled Grid is directly connected; (3) that, in the case of the Participating TO, is imminently likely (as determined in a non-discriminatory manner) to cause a material adverse effect on the security of, or damage to, the Participating TO’s Transmission System, Participating TO’s Interconnection Facilities, Distribution System, or the electric systems of others to which the Participating TO’s electric system is directly connected; or