Underground Cabling Depth Sample Clauses
The Underground Cabling Depth clause sets the required minimum depth at which electrical or communication cables must be buried below ground level. Typically, this clause specifies the exact measurement—such as 18 or 24 inches—and may vary depending on the type of cable, soil conditions, or local regulations. By establishing a standard depth, the clause helps prevent accidental damage during future excavation or construction activities, thereby ensuring safety and compliance with legal requirements.
Underground Cabling Depth. A. Underground electrical cables located outside the perimeter of the (fence) of the solar panels shall be buried with:
1. a minimum of 5 feet of top cover where they cross Cropland.
Underground Cabling Depth. A. Underground electrical cables shall be buried with:
1. a minimum of 5 feet of top cover where they cross Cropland.
2. a minimum of 5 feet of top cover where they cross pastureland or other non- Cropland classified as Prime Farmland.
3. a minimum of 3 feet of top cover where they cross pastureland and other Agricultural Land not classified as Prime Farmland.
4. a minimum of 3 feet of top cover where they cross wooded/brushy land.
B. Provided that the Facility Owner removes the cables during Deconstruction, underground electric cables may be installed to a minimum depth of 18 inches:
1. Within the fenced perimeter of the Facility; or
2. When buried under an access road associated with the Facility provided that the location and depth of cabling is clearly marked at the surface.
C. If Underground Cables within the fenced perimeter of the Facility are installed to a minimum depth of 5 feet, they may remain in place after Deconstruction.
Underground Cabling Depth. A. Underground electrical cables will be buried with: a minimum of 5 feet of top cover where it crosses Cropland. a minimum of 5 feet of top cover where it crosses pasture land or other Agricultural Land comprised of soils that are classified by the USDA as being prime soils. a minimum of 3 feet of top cover where it crosses pasture land and other Agricultural Land not comprised of prime soils.
Underground Cabling Depth. A. Underground electrical cables will be buried with:
1. a minimum of 5 feet of top cover where it crosses Cropland.
2. a minimum of 5 feet of top cover where it crosses pasture land or other Agricultural Land comprised of soils that are classified by the USDA as being prime soils.
3. a minimum of 3 feet of top cover where it crosses pasture land and other Agricultural Land not comprised of prime soils.
4. a minimum of 3 feet of top cover where it crosses wooded/brushy land.
B. Notwithstanding the foregoing, in those areas where (i) rock in its natural formation and/or (ii) a continuous strata of gravel exceeding 200 feet in length are encountered, the minimum top cover will be 30 inches.