The RF. QF shall operate the Facility with all system protective equipment in service whenever the Facility is connected to, or is operated in parallel with, DEF's system, except for normal testing and repair in accordance with good engineering and operating practices as agreed by the Parties. The RF/QF shall provide adequate system protection and control devices to ensure safe and protected operation of all energized equipment during normal testing and repair. All RF/QF facilities shall meet IEEE and utility standards. The RF/QF shall have independent, third party qualified personnel test, calibrate and certify in writing all protective equipment at least once every twelve (12) months in accordance with good engineering and operating practices. A unit functional trip test shall be performed after each overhaul of the Facility's turbine, generator or boilers and results provided to DEF in writing prior to returning the equipment to service. The specifics of the unit functional trip test will be consistent with Prudent Regulated Utility Practices.