Test conditions. A. Start-Up and Stabilization Period. Prior to the start of the test, the Facility shall be started, synchronized and brought to full load using normal start procedures and then operated continuously at full load for as long as it is necessary, but in no case for no less than one hour, for all measured parameters to achieve stable, normal conditions such that any variations in such parameters will be within the tolerances provided in Table 3.3.3 of PTC 22.
Appears in 13 contracts
Samples: Power Purchase Agreement, Power Purchase Agreement, Consent and Agreement
Test conditions. A. Start-Up and Stabilization Period. Prior to the start of the test, the Facility shall be started, synchronized and brought to full load using normal start procedures and then operated continuously at full load for as long as it is necessary, but in no case for no less than one hour, for all measured m easured parameters to achieve stable, normal conditions such that any variations in such parameters will be within the tolerances provided in Table 3.3.3 of PTC 22.