Stator Coolant System Clause Samples

Stator Coolant System. (Where applicable) a) The stator coolant system must have at least one standby AC pump. b) Any filters in the system must be of duplex design to allow cleaning on line and there must be no interruption in flow when changing over. c) Stator coolant filters and heat exchangers must have continuous vents to maintain low conductivity d) Two 100% heat exchangers must be provided. e) The stator coolant water flow of the windings must be in parallel to the circular phase connections and bushings and not in series. f) The stator water inlet temperature must be regulated at a constant temperature. g) Water chemistry must be maintained to Chemistry Standard for Water Cooled Generator Windings 240-55864795 h) The following instrumentation must be fitted as a minimum: