Prudent Electrical Practice Sample Clauses
The 'Prudent Electrical Practice' clause defines the standard of care and diligence expected in the design, installation, operation, and maintenance of electrical systems. It typically requires parties to follow industry-accepted methods, comply with applicable laws and regulations, and use reasonable judgment to prevent harm or inefficiency. For example, it may obligate contractors to use materials and techniques that are widely recognized as safe and reliable within the electrical industry. The core function of this clause is to ensure that all electrical work meets a recognized benchmark of safety and quality, thereby minimizing risks of failure, accidents, or non-compliance.
Prudent Electrical Practice. During the Term, Seller shall be the sole owner of the Electrical Interconnection Facilities. Seller shall defend, indemnify and hold Buyer harmless from and against any requirements to comply with FERC Open Access requirements respecting the Electrical Interconnection Facilities caused by Seller’s act or omission. Seller acknowledges that it shall have no claims under this Agreement against Buyer, acting in its merchant function capacity, with respect to any requirements imposed by or damages caused by Buyer, acting in its transmission function capacity, in connection with the Interconnection Agreement or otherwise.
Prudent Electrical Practice. Seller acknowledges that it shall have no claims under this Agreement against PacifiCorp with respect to any requirements imposed by or damages caused by Transmission Provider, in connection with the Generation Interconnection Agreement or otherwise.
Prudent Electrical Practice. Except for any claims Seller may have in connection with PacifiCorp’s obligation under Section 4.6 in its merchant capacity to take appropriate action and make good faith efforts to pursue applicable remedies on Seller’s behalf, Seller acknowledges that it has no claim under this Agreement against PacifiCorp acting as in its capacity Transmission Provider or Interconnection Provider or with respect to the provision of station service.
Prudent Electrical Practice. During the Term, Seller shall be the sole owner of the Electrical Interconnection Facilities. Seller shall defend, indemnify and hold Buyer harmless from and against any requirements to comply with FERC Open Access requirements respecting the Electrical Interconnection Facilities caused by Seller’s act or omission. Seller acknowledges that it shall have no claims under this Agreement against Buyer, acting in its merchant function capacity, with respect to any requirements imposed by or damages caused by Buyer, acting in its transmission function capacity, in connection with the Interconnection Agreement or otherwise.
6.3.1.2 Without limiting the generality of Section 6.3.1.1, Seller shall:
6.3.1.2.1 At all times, employ qualified and trained personnel for managing, operating and maintaining the Facility and for coordinating such managing, operating and maintenance with Buyer. Seller shall ensure that prior to or on the first Day Seller delivers energy to the Electricity Delivery Point such qualified and trained personnel are available to Buyer at all times, twenty-four (24) hours per Day during the Term.
6.3.1.2.2 Operate and maintain the Facility with due regard for the safety, security and reliability of the System and Buyer’s customers and in compliance with the general specifications contained in Exhibit I.
6.3.1.2.3 Comply with operating and maintenance standards recommended by the Facility’s equipment suppliers.
6.3.1.2.4 Coordinate the Facility’s relaying and protection to conform with Prudent Electrical Practice.
6.3.1.2.5 Furnish and install, at Seller’s sole expense, a manually operable disconnecting device that can be locked by Buyer in the open position and visually checked to be in the open position, so as to be able to electrically isolate the Facility from the System. This device(s) shall be installed at a location at or near the Electricity Delivery Point.
6.3.1.2.6 Have the Facility’s protective relays calibrated and operationally checked, at least annually by a person qualified to perform such service and provide Buyer with a written confirmation of the calibration.
6.3.1.2.7 Operate the Facility in such a manner so as not to have an adverse effect on Buyer’s voltage level or voltage waveform.
6.3.1.2.8 Operate the Facility in a manner and consistent with the Operating Procedures so as to permit Buyer to dispatch individuals items of Major Equipment required to generate energy Scheduled by Buyer.