Net Dependable Clause Samples
Net Dependable. Capacity Evaluation -------------------------------------- Generator Net Power Output -------------------------- Generator Net Power Output (GNPO) will be calculated from the measured net power output from the test point divided by the test point duration in hours. GNPO = measured net power output (kWh) / test point duration (hrs.) Net Dependable Capacity ----------------------- Generator Net Power Output (GNPO) will be corrected from the test conditions to the Reference Conditions. The result will be the Net Dependable Capacity (NDC). NDC = Net Dependable Capacity corrected to Reference Conditions. NDC = GNPO x CF\\1\\ x CF\\2\\ x CF\\3\\ where: CF\\1\\ = Factor used to correct power from the measured ambient temperature and humidity to the contract conditions = CF\\a\\ / CF\\b\\ where: CF\\a\\ = Ambient temperature and humidity correction factor from GE Curve [insert curve number when received from GE] at the Reference Conditions CF\\b\\ = Ambient temperature and humidity correction factor from GE Curve [insert curve number when received from GE] at the measured ambient temperature and humidity CF\\2\\ = Factor used to correct power from the measured barometric pressure to the rated barometric pressure = P\\R\\ / P\\M\\ where: P\\R\\ = Rated barometric pressure (14.39 psia) P\\M \\= Measured barometric pressure CF\\3\\ = Factor used to correct for accumulated fired hours prior to the test = 1 + (% output loss from curve 519HA772) The NDC's determined from each test point will be summed and divided by the number of test points to determine the NDC for contract purposes.