MOUNTING REQUIREMENTS Sample Clauses
MOUNTING REQUIREMENTS. A. Unless the equipment incorporates unit construction using an integral rigid frame or is specified otherwise, mount each item of mechanical equipment along with its drive unit on rigid steel or steel and concrete base.
B. Cast iron bases: not permitted when equipment is furnished with a vibration isolation system.
MOUNTING REQUIREMENTS. A. All anchorage of equipment is to be made of poured-in-place concrete elements; it is imperative that anchorage be coordinated with the concrete work so that anchorage may be installed at time of pouring. If submittal of calculations and anchorage details are not approved prior to pouring of concrete, be responsible for any strengthening of concrete elements.
B. For belt driven equipment shown as in-line and piggyback, the base shall be rectangular and the motor shall always be behind and above the driven equipment and never over the driven equipment unless approved by the Project Representative. Motor mounting hardware for any belt driven configuration shall allow for belt tension adjustment. May 2017 C01025C17 Georgetown Wet Weather Treatment Station 11050 - 2 GENERAL EQUIPMENT MOUNTING
C. Provide supports, anchorage, and mounting of equipment in accordance with the manufacturer's recommendations, the SBC, and industry standards requirements.
D. Provide elements required to resist the calculated forces described herein or required by the equipment manufacturer.
E. Design anchorage for equipment bases, supports, and foundations in accordance with SBC and Section 01031.
F. For equipment 15 horsepower and larger, anchor bolt calculations showing adequacy of bolt sizing and anchor embedment shall be prepared, stamped, dated, and signed by a Professional Engineer registered in the state of Washington.