Manual Disconnect Switch. 5.1. Participant must install an exterior manual, lockable, visible load break AC disconnect switch between the inverter and MLGW’s meter socket. For Qualifying Systems using micro-inverters, a fused AC disconnect switch must be used. (An optional DC disconnect switch is recommended between the generation source and inverter.) The AC switch must be visibly marked “
Appears in 2 contracts
Samples: And Parallel Operation Agreement, And Parallel Operation Agreement
Manual Disconnect Switch. 5.1. Participant must install an exterior a manual, lockable, visible load break AC disconnect switch between the inverter and MLGW’s meter socket. For Qualifying Systems using micro-inverters, a fused AC disconnect switch must be used. (An optional DC disconnect switch is recommended between the generation source and inverter.) The AC switch must be visibly marked “
Appears in 2 contracts
Samples: Operation Agreement, Operation Agreement
Manual Disconnect Switch. 5.1. Participant must install an exterior manual, lockable, visible load break AC disconnect switch between the inverter and MLGW’s meter socket. For Qualifying Systems using micro-inverters, a fused AC disconnect switch must be used. (An optional DC disconnect switch is recommended between the generation source and inverter.) The AC switch must be visibly marked “a
Appears in 1 contract
Samples: And Parallel Operation Agreement