Common use of Manual Disconnect Switch Clause in Contracts

Manual Disconnect Switch. 5.1 FPL shall require the Customer to install, at the Customer’s expense, a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the Customer-owned renewable generation and any Customer wiring connected to FPL’s system. The manual disconnect switch shall be mounted separate from, but adjacent to, the FPL meter socket. The Customer shall ensure that such manual disconnect switch shall remain readily accessible to FPL and be capable of being locked in the open position with a single FPL utility padlock.

Appears in 5 contracts

Samples: Agreement, Agreement, Agreement