Manual Disconnect Switch. 12.01. Customer shall install a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the CRG system and any Customer wiring connected to Utility’s electric system such that back feed from the CRG system to Utility’s electric system cannot occur when the switch is in the open position. The manual disconnect switch shall be mounted separate from the meter socket on an exterior surface adjacent to the meter. The switch shall be readily accessible to Utility and capable of being locked in the open position with a Utility padlock. When locked and tagged in the open position by Utility, this switch will be under the control of Utility.
Appears in 19 contracts
Samples: Billing Power Purchase Agreement, Interconnection Agreement, Interconnection Agreement
Manual Disconnect Switch. 12.01. Customer shall provide and install a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the CRG customer-owned renewable generation system and any Customer wiring connected to Utility’s electric system such that back feed from the CRG customer-owned renewable generation system to Utility’s electric system cannot occur when the switch is in the open position. The manual disconnect switch shall be mounted separate from the meter socket on an exterior surface adjacent to the meter. The switch shall be readily accessible to Utility and capable of being locked in the open position with a Utility padlock. When locked and tagged in the open position by Utility, this switch will be under the control of Utility.