Common use of load test Clause in Contracts

load test. The regen or terminal load test will be performed by isolating the commercial power and running the generator with the full power load for minimum of thirty minutes. While the generator is supplying the power all functions within the regen/terminal must be monitored by on site personnel along with the generator gauges. Once load test is performed, commercial power will be restored and performance checks monitored for fifteen minutes before departing site. IFN EXHIBIT 13 SITE POWER SPECIFICATIONS ------ CONTENTS PARAGRAPH CONTENTS -------- --------- -------- GENERAL 1.0 SPECIFIC POWER 2.0 REQUIREMENTS

Appears in 1 contract

Sources: Fixed Fee Agreement (Itc Deltacom Inc)

load test. The regen or terminal load test will be performed by isolating the commercial power and running the generator with the full power load for a minimum of thirty minutes. While the generator is supplying the power all functions within the regen/regen/ terminal must be monitored by on on-site personnel along with the generator gauges. Once load test is performed, commercial power will be restored and performance checks monitored for fifteen minutes before departing site. IFN EXHIBIT 13 SITE POWER SPECIFICATIONS ------ CONTENTS PARAGRAPH CONTENTS -------- --------- -------- GENERAL 1.0 SPECIFIC POWER 2.0 REQUIREMENTSSECTION FIVE ATTACHMENTS

Appears in 1 contract

Sources: Fixed Fee Agreement (Itc Deltacom Inc)