Inverter Capacity Clause Samples
Inverter Capacity. The Community Solar Garden must have an inverter with a capacity of no more than one (1) megawatt alternating current (AC) to assure that the Community Solar Garden has a nameplate capacity of no more than one (1) megawatt AC.
Inverter Capacity. The static inverter shall have the following minimum capabilities. Continuous full load rating The inverter shall be sized to supply power for 110 percent of the plant's critical 120 volt ac loads Step load pickup Upon transfer of full load, the inverter output voltage shall not drop below 75 percent of nominal voltage during the first half cycle after transfer and 90 perent of nominal voltage. Fuse clearing Upon a fault in any branch circuit lateral feeder, the inverter shall have the capacity to carry a load equal to one-half of its full load rating and clear a 30 ampere fast acting fuse in 4 milli-seconds (1/4 cycle) or less. This requirement shall be met if the static switch fails to transfer from the inverter to the alternate source.
Inverter Capacity. The CBRE Project must have an inverter(s) with a capacity, in the aggregate, of no more than ( ) kilowatts/megawatts alternating current (AC) to assure that the CBRE Project has a nameplate capacity of no more than ( ) kilowatts/megawatts AC.