Fire Protection Panel Clause Samples

Fire Protection Panel. Monitoring System (CEMS). - Emergency generator(s) - Critical control room lighting. air intake louver motors, radiator fan motors. - Plant computer local area network and FAX machines. - Programmable Logic Controller for chemical treatment of them main water treatment plant. - Battery rooms ventilation fans. - High Pressure and Intermediate Pressure Boiler drum level controllers. - Plant Surveillance Cameras and Monitors. The following equipment shall be designed and assembled to provide 120/208 volt, three-phase, 60-hertz power to a 4 wire isolated grounded uninterruptible ac power system. Quantity Description 1 Static inverter 1 Full capacity static switch 1 120/208 volt ac distribution panelboard 1 Manual bypass switch
Fire Protection Panel. The Plant fire panel shall be located in the PCR. System shall be fail safe using resistors to detect wiring discontinuities. A closed contact shall be the normal condition and an open contact shall be the alarm condition. Fire/smoke alarms shall be dry contacts. Fire/smoke detectors shall be installed in all buildings and walk-in enclosures, including: Building SA Building SB (Optional) Building SC CTG enclosures STG enclosure BOP electrical equipment enclosures CEMS enclosures