Existing Building Security System. (1) Contractor shall comply with Princeton University Department of Site Protection and Public Safety Department protocols and approval processes before disarming, altering, rendering inoperable or otherwise performing any work on existing building security systems.
(2) If any existing building access control/security system is disturbed, altered, or relocated during the course of the Work, the entire security system shall be tested by the Contractor and approved by Princeton University’s Alarm Shop prior to acceptance of the Work.
(3) The Contractor shall not tape any door latches, prop open doors and/or windows normally locked without prior approval of Princeton University’s Department of Public Safety and notification to Princeton University’s Department of Site Protection and building occupants.
(4) Contractor shall be responsible for the sign out, distribution, safe use, and return of all keys and/or access cards for the existing building. The Contractor shall be responsible for all costs associated with failure to return these items (e.g., the cost to re-key/re-implement the system, etc.).
(5) Contractor shall coordinate with Princeton University’s Department of Site Protection to commission all new access control/security systems. All new access control/security installations and/or systems shall be tested by the Contractor and approved by Princeton University’s Department of Site Protection prior to acceptance of the Work.