Environment Availability Clause Samples

Environment Availability. The Supplier guarantees 99.999% availability of 23 +/- 3°C air temperature within the cold aisle in which the Client’s equipment is installed measured by the average reading of the sensors located at the top and base of each cold aisle during each 24 hours beginning at midnight. If during any such 24 hour period this Service Level is breached where during the period in question the maximum outside temperature exceeded 33°C or the minimum outside temperature was lower than -5°C, Clause 4.4 below shall not apply. All specified cooling levels assume that the Client will configure equipment installed in a rack in accordance with best industry practice for a cold and hot aisle environment to minimise the build-up of heat within the rack cabinet space. To ensure that cooling levels are effectively regulated, it is the Client’s responsibility to fit blanking plates to completely fill any empty spaces left at the front of its rack space, following the installation of equipment. Blanking plates are available from the Supplier as chargeable items