DC Field. 3.2.1.1. For each combiner box measure and record the resistance to the combiner boxes to the North and/or South.
3.2.1.2. For each interior ground rod measure and record the resistance between it and the ground rods immediately to the North and/or South.
3.2.1.3. Measure and record the resistance between the bonding jumper on the second motor of each drive line to the jumper on the second motor immediately to the North and South on adjacent drive lines.
3.2.1.4. Measure and record the resistance from the ground wire at the end of each cable tray to the ground well at power station it feeds.
3.2.1.5. Within each power station make 4 spot check measurements between the cable trays and the bonding jumper on a post farthest from the cable tray on the same drive line and record the resistance.