Cooling Availability. Target ambient room temperature will be 22 Degrees Celcius in the server area of the Data Centre. Ambient room temperature will not vary by more than +/- 1 degree. BT shall guarantee that the Cooling Availability on the Heating Ventilation and Air Conditioning (HVAC) facilities within the BT Suite upto 99.99% in a calendar month based on the following formulae. TotalAvailableTime − TotalOutage Cooling Availability (%) = .
Appears in 1 contract
Cooling Availability. Target ambient room temperature will be 22 Degrees Celcius in the server area of the Data Centre. Ambient room temperature will not vary by more than +/- 1 degree. BT shall guarantee that the Cooling Availability on the Heating Ventilation and Air Conditioning (HVAC) facilities within the BT Suite upto 99.99% in a calendar month based on the following formulae. TotalAvailableTime − TotalOutage Cooling Availability (%) = .
Appears in 1 contract
Sources: Data Centre Hosting Agreement