Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 31 contracts
Sources: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 15 contracts
Sources: Transmission Service Agreement, Transmission Service Agreement, Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits, which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 1 contract
Sources: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/remote/ local whereas the earth switches shall have local control only.
Appears in 1 contract
Sources: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/substation/ switching stations shall be controlled and synchronized from the switchyard control room/room/ remote control center. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/remote/ local whereas the earth switches shall have local control only.
Appears in 1 contract
Sources: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control center. All the isolators shall have control from remote/local whereas the earth switches shall have local control only. However, the prevailing practice as per GIS Substations may be adopted.
Appears in 1 contract
Sources: Transmission Service Agreement
Control Concept. All the EHV circuit breakers in substation/switching stations shall be controlled and synchronized from the switchyard control room/remote control centercentre. Each breaker would have two sets of trip circuits which would be connected to separate DC supplies for greater reliability. All the isolators shall have control from remote/local whereas the earth switches shall have local control only.
Appears in 1 contract
Sources: Transmission Service Agreement