COMBINED-CYCLE PROJECTS Sample Clauses
COMBINED-CYCLE PROJECTS. The Borrower will conduct a 7-day reliability test which is intended to demonstrate that each of the Autaugaville 1 Project, the Autaugaville 2 Project, the Goat Rock 1 Project, the Goat Rock 2 Project and the Wansley Project (and any other Subsequent Project which is a com▇▇▇▇▇-▇ycle electric generation plant) are capable of continuous, reliable operation at various load points. The reliability test shall be conducted during a continuous 168-hour period during which the relevant Project shall demonstrate the following requirements: o Achieve an Equivalent Availability Factor (as calculated by the North American Electric Reliability Council) of at least 97 percent; o During such test, the Project shall operate for 124 or more hours at the mode of operation applicable to either the Guaranteed Output or the Guaranteed Heat Rate for such Project, provided that the Project shall operate (a) for at least 24 hours in the mode of operation applicable to the Guaranteed Output for such Project, if ambient conditions allow; and (b) for at least 6 continuous hours in the mode of operation applicable to the Guaranteed Output for such Project; o During the reliability test, data will be recorded from plant instrumentation at one-hour intervals (ambient conditions recorded manually if necessary); o All plant emissions shall be recorded by the plant CEMS during the reliability test; o During the reliability test, the Project shall be operated in accordance with prudent utility practice and all laws, permits and regulations applicable to such Project (including, without limitation, all emissions requirements imposed by the Project's air permit); and o The facility controls shall be placed in an "automatic mode" to an extent consistent with normal operating practice, and manual control of facility equipment and systems shall be minimized. Operating personnel shall be staffed consistent with normal operating plans.
COMBINED-CYCLE PROJECTS. The Borrower will conduct a 7-day reliability test which is intended to demonstrate that each of the Harris 1 Project, the Harris 2 Project, the Franklin 1 Project, t▇▇ ▇▇▇nklin 2 Project ▇▇▇ ▇▇e Wansley Project (and any other Subsequent Project which is a comb▇▇▇▇-▇▇cle electric generation plant) are capable of continuous, reliable operation at various load points. The reliability test shall be conducted during a continuous 168-hour period during which the relevant Project shall demonstrate the following requirements: o Achieve an Equivalent Availability Factor (as calculated by the North American Electric Reliability Council) of at least 97 percent; o During such test, the Project shall operate for 124 or more hours at the mode of operation applicable to either the Guaranteed Output or the Guaranteed Heat Rate for such Project, provided that the Project shall operate (a) for at least 24 hours in the mode of operation applicable to the Guaranteed Output for such Project, if ambient conditions allow; and (b) for at least 6 continuous hours in the mode of operation applicable to the Guaranteed Output for such Project;