Circuit Protective Devices. 1. One (1) 242 KV, 2000A, outdoor, deadtank, SF6 gas puffer circuit breakers 40 KA maximum symmetrical interrupting current, 60 HZ, 3 cycle interrupting time, hydraulic spring drive operating mechanism. Breaker includes 12-2000:5 C800 multi-ratio relay accuracy bushing current transformers. 2. Steel reinforced foundations for the Circuit Protective Device. 3. One (1) lot of aluminum bus, suitable connectors, clamps, etc.
Circuit Protective Devices. 1. Two (2) 242 KV, 1200A, outdoor, SF6 gas puffer circuit switcher 20 KA maximum symmetrical interrupting current, 60HZ, 6 cycle interrupting time, with a vertical break disconnect manual drive operating mechanism. 2. Nine (9) 38 KV, 1200A, outdoor, deadtank, vacuum circuit breakers having a 38 KV maximum voltage; 150 KV BIL phase-to-ground, 20 KA maximum symmetrical interrupting current, 60HZ, 3 cycle interrupting time, spring operating mechanism. Breaker includes 6-1200:5 C400 multi ratio relay accuracy bushing current transformers. 3. Steel reinforced foundations for the Circuit Protective Devices. 4. One (1) lot of aluminum bus, suitable connectors, clamps, etc. for connecting the Protective Devices.