Chases. (2/G/6) Where xxxxxxx is cut, holed or chased for conduits, pipes or the like, all such chases shall be filled in solid with cement mortar mix (1:4) prior to the application of finishes. In no case shall the vertical chase be deeper than one third the thickness of the wall and in no case shall the horizontal chase be deeper than one sixth the thickness of the wall.