CABLE INSTALLATIONS. A. Depending upon the extent of the work, Customer should consider the disabling of the fire alarm enunciation, smoke detection and suppression systems. B. The following requirements only apply to shared, common space outside of the Customer leased space. Customer cable work inside customer premises is exempt; provided 1. Customer must use good workmanship and engineering practices. 2. No “Customer to Customer” cable connections are permitted between DLR Customers in the Datacenter. Customers are allowed to interconnect between any of their owed equipment and their customer’s within their leased premises. 3. The under floor cable management is to be used for all cable runs. 4. Customer may run overhead ladder rack or tray affixed to the top of customer cabinets within customer’s premises, as necessary. 5. All cables installations must be secured and bundled together using the approved materials such as wax-coated string, Velcro-ties or plastic tie-straps. 6. Cables are not allowed to extend beyond the rack/tray edges. Cable bundles will be kept in a neat and orderly fashion to maintain workability and appearance. 7. All cables must be run on top of the rack/tray and are not allowed to be run underneath them.
Appears in 1 contract
CABLE INSTALLATIONS. A. Depending upon the extent of the work, Customer should consider the disabling of the fire alarm enunciation, smoke detection and suppression systems.
B. The following requirements only apply to shared, common space outside of the Customer leased spaceColocation Premises. Customer cable work inside customer premises is exempt; provided
1. Customer must use good workmanship and engineering practices.
2. No “Customer to Customer” cable connections are permitted between DLR Customers in the Turn-Key Datacenter™. Customers are allowed to interconnect between any of their owed equipment and their customer’s within their leased designated premises.
3. The under floor cable management is to be used for all cable runs.
4. Customer may run overhead ladder rack or tray affixed to the top of customer cabinets within customer’s premises, as necessary.
5. All cables installations must be secured and bundled together using the approved materials such as wax-coated string, Velcro-ties or plastic tie-straps.
6. Cables are not allowed to extend beyond the rack/tray edges. Cable bundles will be kept in a neat and orderly fashion to maintain workability and appearance.
7. All cables must be run on top of the rack/tray and are not allowed to be run underneath them.
Appears in 1 contract