C standard Sample Clauses
C standard. As a protection against termite attack the outer covering shall preferably contain an evenly dispersed mixture of aldrin and dieldrin in the ratio of 0.25% aldrin and 0.25% dieldrin by weight of PVC, or another suitable deterrent which shall be stated in the tender for approved by the Engineer. The contractor shall stage on the cable test certificate the amounts of insecticide added. The Engineer reserves the right to select samples of such outer coverings for analysis to check the quantities added.
C standard. As a protection against termite attack the outer covering suitable deterrent which shall be stated in the tender for approved by the Engineer. The contractor shall stage on the cable test certificate the amounts of insecticide added. The Engineer reserves the right to select samples of such outer coverings for analysis to check the quantities added.
i. Voltage – Identification: The plastic over sheath shall be embossed with the name of the manufacturer followed by: IDECO, Electric cables – 33 KV – (Cable size) Contract No numerals shall comply with the requirements of BS 6346, or equivalent. --/----, the letters and
j. Sealing: Immediately after the works tests, both ends of the cable shall be sealed against the ingress of moisture, dirt and insects and the end projecting from the drum shall be adequately protected against mechanical damage during handling and shall be fitted with heat shrink end cap or equivalent for cores, sheath and armors.
C standard. As a protection against termite attack the outer covering suitable deterrent which shall be stated in the tender for approved by the Engineer. The contractor shall stage on the cable test certificate the amounts of insecticide added. The Engineer reserves the right to select samples of such outer coverings for analysis to check the quantities added.