Common use of Automatic Control Service Type Clause in Contracts

Automatic Control Service Type. a) Pursuant to Art. II.3.10, each Controlling Technical Unit must be able to adjust its Reactive Power production or absorption automatically in the event of Grid Voltage variation at its Service Measurement Point, in accordance with the relative Sensitivity Coefficient αeq as defined in Annex 1. b) To ensure that the automatic regulator of a Controlling Technical Unit provides the Automatic Control Service Type correctly, ▇▇▇▇ verifies whether the Reactive Power actually supplied by the Technical Unit corresponds to the Reactive Power that should have been supplied in response to variations of the Grid Voltage measured at that same Service Measurement Point. c) ▇▇▇▇ uses quarter-hourly metering data to carry out this verification monthly for each Technical Unit for delivery in Month M-2, starting out with six samples. Each sample pertains to a 5-hour period. ▇▇▇▇ applies the penalty described in Art.II. 9.1 where necessary. d) Delivery control criteria, modalities and non-supplied volume calculation for the Automatic Control Service Type are described in Annex 3. e) In any case, Grid Voltage according to which regulation is performed is measured at the Service Measurement Point according to modalities of Art. II.6.

Appears in 2 contracts

Sources: Voltage & Reactive Power Control Service Contract, Voltage & Reactive Power Control Service Contract