Analog Points Sample Clauses

Analog Points. Analog inputs to the generation-specific RTU shall be supplied from a TSP-approved interface device or hardwired. Analog point RTU inputs from a TSP-approved interface device shall be RS-232 (with optical isolation) or RS-485 using DNP 3.0 protocol. 1) Generation ▇▇▇▇▇ ▇▇ (required for each thermal-powered generation unit) 2) Generation gross MVAR (bi-directional values required for each thermal-powered generation unit) 3) Generation station use MW auxiliary (required for each auxiliary transformer) 4) Generation station use MVAR auxiliary (bi-directional values required for each auxiliary transformer) 5) Station frequency HZ (for those stations where a common bus does not exist between multiple generation units, individual unit frequency points will be required) 6) Voltage per phase for each winding of each transformer 7) Current per phase for each winding of each transformer 8) MW for each winding of each transformer 9) MVAR for each winding of each transformer (bi-directional values required) 10) MW for each circuit breaker/switcher in the station 11) MVAR for each circuit breaker/switcher in the station (bi- directional values required) 12) MW for each collection feeder 13) MVAR for each collection feeder (bi-directional values required) 14) Voltage per phase of each collection feeder 15) Voltage per phase of each shunt device (capacitor and reactor) 16) MVAR for each shunt device (capacitor and reactor) (bi- directional values required) 17) Tap position for each power transformer 18) Dynamic MVAR capability at the current MW generation amount (required for each dynamic reactive controller) 19) Voltage set point for each dynamic reactive controller 20) Power factor set point for each dynamic reactive controller
Analog Points. Total Generation (MW)
Analog Points. The following RTU inputs shall be supplied from a TSP- approved interface device. RTU inputs from a TSP-approved interface device shall be RS-232 (with optical isolation) using DNP 3.0
Analog Points. 10.4.1 115kV Bus voltage 10.4.2 Generator #1 (MW) 10.4.3 Generator #1 (MVAR) 10.4.4 Generator #2 (MW) 10.4.5 Generator #2 (MVAR) Deep Creek Station - 3 55 SCHEDULE A PINEY STATION INTERCONNECTION FACILITIES 1. Description of Points of Interconnection 1.1
Analog Points. 10.4.1 Total Generation (MW) 10.4.2 Total Generation (MVAR) Blossburg Station - 3 52 SCHEDULE A DEEP CREEK HYDRO STATION INTERCONNECTION FACILITIES 1 Description of Points of Interconnection
Analog Points. 10.4.1 Generator #4 Actual Generation (MW) 10.4.2 Generator #4 Actual Generation (MVAR) 10.4.3 Generator #5 Actual Generation (MW) 10.4.4 Generator #5 Actual Generation (MVAR) Sewa▇▇ ▇▇▇tion - 5 SCHEDULE A SHAWVILLE STATION INTERCONNECTION FACILITIES 1 Description of Points of Interconnection
Analog Points kV Bus potential (V)
Analog Points. 10.3.1 Generator #1 (MW) 10.3.2 Generator #1 (MVAR) 10.3.3 Generator #2 (MW) 10.3.4 Generator #2 (MVAR) 10.3.5 Generator #3 (MW) 10.3.6 Generator #3 (MVAR) 10.3.7 Generator #4 (MW) 10.3.8 Generator #4 (MVAR)
Analog Points. Generator #1 (MW)