Alarms. The Site should have at least the following custom alarms: (a) Inverter produces less than ten percent (10%) of the inverter capacity over the course of an hour between 10am and 3pm. The upper limit of the alarm should be set to twice the inverter capacity. (b) Generation Meter reports less than 0.1 kW for one hour between 10am and 3pm. The upper limit of the alarm should be set to twice the site capacity.