Air-Conditioning & Mechanical Ventilation System Sample Clauses
Air-Conditioning & Mechanical Ventilation System a. If you require to install additional Air-Conditioning System for the Premises, you must first discuss with our agent, Ascendas Services Pte Ltd to explore the feasibility of tapping the Building’s chilled water.
i. For Chilled Water Air-Conditioning System, only system with average operating Total System Efficiency (water-side efficiency + air-side efficiency) as stated in Table 2 below is allowed. The system must be installed with Measurement & Verification equipment to determine the Total System Efficiency with capability to download the data for G▇▇▇▇ ▇▇▇▇ submission purposes. You must submit the Total System Efficiency computation, Our Initials Your Initials K.K. F.E. technical specification and evidence of achieving the targeted efficiency to us for approval before installation.
ii. For Variable Refrigerant Flow (VRF) System, only system with average operating Total System Efficiency (include air-side efficiency) as stated in Table 2 below is allowed. The system must be installed with Measurement & Verification equipment to determine the Total System Efficiency with capability to download the data for G▇▇▇▇ ▇▇▇▇ submission purpose. You must submit the Total System Efficiency computation, technical specification and evidence of achieving the targeted efficiency to us for approval before installation. You shall ensure VRF Systems are installed with the following provisions:
1) For new or replacement of VRF Systems, as well as new distribution system serving combined floor area of 2000m2 or more, permanent measurement and verification system should be installed to examine the efficiency of the total system. Connections to our Building Management System should be provided where technically viable, and such performance data shall be made available to the Landlord as and when necessary.
2) Temperature sensors and occupancy sensors shall be installed to control energy usage. Enclosed areas not served by the central cooling system shall be provided with dedicated thermostat controls (including but not limited to meeting rooms, closed offices and conference facilities) with auto shut off or ramp down when not in use.
iii. For Unitary Air-Conditioning (AC) System, only system with energy label of min 4 Ticks for Three-Phase System or min 5 Ticks for Single-Phase System as stated in Table 3 below is allowed. You must submit the technical specifications to us for approval before installation. Our Initials Your Initials K.K. F.E.
b. You must only use energy eff...