Common use of Accessible toilets Clause in Contracts

Accessible toilets. ENERGY: HVAC Performance: General office and common area shall be heated in the winter to maintain the space environment at 68 – 74 degrees Fahrenheit (F) with a relative humidity of 20 – 30 % and cooled in the summer at 68 – 78 degrees F with a relative humidity of 40 – 60 %. The HVAC system must be capable of maintaining +/- two (2) degrees F of the thermostat setting. As a guide, an adequately sized air distribution system shall provide 4 – 10 air changes per hour. HVAC equipment shall be properly sized and balanced to meet design conditions. Each zone provided shall be equipped with programmable thermostatic controls, capable of a 55 degree F night/weekend setback in the heating mode and a 85 degree F night/weekend set-up in the cooling mode. Heating system efficiency will not be less than 80% steady state at full load for natural gas boilers or furnaces. Air conditioning equipment will meet or exceed the performance ratings required under Federal and State guidelines. A seven-day programmable time device will control all air handling systems where applicable controls exist. Minimum ventilation rates will be capable of 15 cubic feet per minute per person during occupied hours and automatically reduced during off-work hours. Buildings are to be in full compliance with the ANSI/ASHRAE/IESNA Standard 90.1 latest edition, Energy Design of New/Existing Commercial Buildings. Telecommunication, Computer, UPS and server room(s) require air conditioning systems designed to ensure proper environmental requirements are met. These rooms shall be maintained between 65 & 72 degrees F. The HVAC system must be capable of maintaining +/- two (2) degrees F of the thermostat setting. This condition must be maintained 24 hours a day, seven (7) days a week. HVAC shall be thermostatically controlled within the room and be independent of the house system. Two Kansas Administrative Regulations, (1-66-1 and 1-66-3), became effective February 4, 2011, requiring the completion of an energy audit for lease space. The K.A.R.’s require that each new lease, lease renewal or extension must include an energy audit for lease property. In the event the energy audit indicates that the lease space uses an excessive amount of energy, the owner or lessor is required to implement cost effective energy conservation measures that are approved by the Secretary of Administration to eliminate excessive amounts of energy usage. ADDITIONAL REQUIRED DOCUMENTS CHECKLIST: The following documents must be submitted with the signed Lease:

Appears in 4 contracts

Samples: Real Estate Lease Agreement, Real Estate Lease Agreement, Real Estate Lease Agreement

AutoNDA by SimpleDocs

Accessible toilets. ENERGY: HVAC Performance: General office and common area shall be heated in the winter to maintain the space environment at 68 – 74 degrees Fahrenheit (F) with a relative humidity of 20 – 30 % and cooled in the summer at 68 – 78 degrees F with a relative humidity of 40 – 60 %. The HVAC system must be capable of maintaining +/- two (2) degrees F of the thermostat setting. As a guide, an adequately sized air distribution system shall provide 4 – 10 air changes per hour. HVAC equipment shall be properly sized and balanced to meet design conditions. Each zone provided shall be equipped with programmable thermostatic controls, capable of a 55 degree F night/weekend setback in the heating mode and a 85 degree F night/weekend set-up in the cooling mode. Heating system efficiency will not be less than 80% steady state at full load for natural gas boilers or furnaces. Air conditioning equipment will meet or exceed the performance ratings required under Federal and State guidelines. A seven-day programmable time device will control all air handling systems where applicable controls exist. Minimum ventilation rates will be capable of 15 cubic feet per minute per person during occupied hours and automatically reduced during off-work hours. Buildings are to be in full compliance with the ANSI/ASHRAE/IESNA Standard 90.1 latest edition, Energy Design of New/Existing Commercial Buildings. Telecommunication, Computer, UPS and server room(s) require air conditioning systems designed to ensure proper environmental requirements are met. These rooms shall be maintained between 65 & 72 degrees F. The HVAC system must be capable of maintaining +/- two (2) degrees F of the thermostat setting. This condition must be maintained 24 hours a day, seven (7) days a week. HVAC shall be thermostatically controlled within the room and be independent of the house system. Two Kansas Administrative Regulations, (1-66-1 and 1-66-3), became effective February 4, 2011, requiring the completion of an energy audit for lease space. The K.A.R.K.A.R’s require that each new lease, lease renewal or extension must include an energy audit for lease property. In the event the energy audit indicates that the lease space uses an excessive amount of energy, the owner or lessor is required to implement cost effective energy conservation measures that are approved by the Secretary of Administration to eliminate excessive amounts of energy usage. ADDITIONAL REQUIRED DOCUMENTS CHECKLIST: The following documents must be submitted with the signed Lease:

Appears in 1 contract

Samples: Real Estate Lease Agreement

AutoNDA by SimpleDocs
Time is Money Join Law Insider Premium to draft better contracts faster.