Interconnection Customer’s Interconnection Facilities Sample Clauses

Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall design, procure, construct, install, own and/or control the Interconnection Customer’s Interconnection Facilities described in Appendix A at its sole expense.
AutoNDA by SimpleDocs
Interconnection Customer’s Interconnection Facilities. Interconnection Customer shall, at its expense, design, procure, construct, own and install the ICIF, as set forth in Appendix A.
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall:
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line diagram in Attachment 3, the ICIF consist of the following:
Interconnection Customer’s Interconnection Facilities. As depicted on the one-line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) consist of the following:
Interconnection Customer’s Interconnection Facilities. All facilities and equipment, as identified in Section 1(a) of this Attachment 2 of this SGIA, that are located between the Small Generating Facility and the Point of Change of Ownership, including any modification, addition, or upgrades to such facilities and equipment necessary to physically and electrically interconnect the Small Generating Facility to the Distribution System. Interconnection Customer's Interconnection Facilities are sole use facilities.
Interconnection Customer’s Interconnection Facilities. As depicted on the one-line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) consist of the following: Scipio Solar Collector Substation • One (1) 38 kV, 600 A, 25 kA circuit breaker;
AutoNDA by SimpleDocs
Interconnection Customer’s Interconnection Facilities. One (1) transformer, generator step-up, station service; three-phase, 7.25% impedance; 2500/3125 55 degreesC kVA; primary voltage 34.5 kV, 200 kV BIL; secondary voltage 480 V, 45 kV BIL; wye-wye; primary fuse XX0, 000X, Xxx. One (1) transformer, generator step-up, station service; three phase, 7.85% impedance; 2500/3125 55 degrees C, 2800/3500 65 degrees C; primary voltage 34,400, secondary voltage 480/277; wye-wye; primary fuse XX0, 000X, Xxx. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100 amp; interrupting capability 6250 kA. One (1) primary fuse XX0, 000X, Xxx. transformer protection device, 34.5 kV nominal, 38 kV max; 200 kV BIL; 100E amp, interrupting capability of 6250 kA. One (1) Alduti-Rupter three-phase manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont.,40 kA momentary, 600 amp interrupting capability. One (1) AR116SFCLW three phase, manual/group operated disconnect switch, 34.5 kV nominal, 38 kV max, 200 kV BIL, 600 amp cont., 40 kA momentary, 600 amp interrupting. Eighteen (18) surge arrestors type 27 kV, 22 kV, MCOV, intermediate class.
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer shall design and construct the Interconnection Customer’s Interconnection Facilities and Jointly Owned Interconnection Facilities in accordance with the applicable requirements of Connecting Transmission Owner, as set out in National Grid Electric System Bulletin 756, dated May 2007, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT, and in accordance with the Connecting Transmission Owner’s project specific electrical requirements, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT. As depicted in Attachment 3, Figure 1, for the Interim Constrained Operation Interconnection (“ICOI”), the Interconnection Customer Interconnection Facilities and the Jointly Owned Interconnection Facilities consist of: Equipment in Switchgear cubicle 8A, which constitute Interconnection Facilities that are for the sole use of the Interconnection Customer’s Small Generating Facility (Steel Winds II), including, but not limited to: One (1) 13.8 kV, 1200 A feeder breaker with 29 kA interrupting capability; Three (3) 12 kV station class surge arresters; Four (4) sets of single phase, 1200:5 CTs; One (1) set of single phase, 3000:5 CTs; New Jointly Owned Interconnection Facilities that are for the joint use of Niagara Wind Power’s existing Steel Winds I facility and the Small Generating Facility (Steel Winds II), including: Two (2) reverse power relays will be installed by the Developer on the low side of the transformer for limiting the export on each of the Lines 149 and 150 to 10MW or less. The Existing Collection Station, which constitutes the remainder of the Jointly Owned Interconnection Facilities for the ICOI that are for the joint use of Niagara Wind Power’s existing Steel Winds I facility and the Small Generating Facility (Steel Winds II), including: One (1) 13.8 kV, 2500 A bus tie breaker with 29 kA interrupting capability; Relaying; One (1) 3Ph, 75 kVA 13800/480-277V station service transformer; Six (6) 115 kV surge arresters; Two (2) 25/33/41.6 MVA OA/FA/FA, 115/13.8Y kV GRD Wye/7970V (two winding) transformers; Two (2) 13.8 kV, 2500 A breakers with 29 kA interrupting capability; Two (2) 115 kV, 1200A, 550 kV BIL oil circuit breakers with 22 kA interrupting capability; Two (2) 115 kV, 1200A motor operated, oil circuit breaker disconnect switches; Two (2) 115 kV, 1200 A, motor operated line disconnect switches; and Two (2) 115 kV, 1200 A, motor operated tie disconnect switches. ...
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer constructed the Interconnection Customer’s Interconnection Facilities in accordance with the applicable requirements of Connecting Transmission Owner, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT, and in accordance with the Connecting Transmission Owner’s project specific electrical requirements, to the extent not inconsistent with the terms of this Agreement or the NYISO OATT. As depicted in Attachment 3, Figures 1 and 2, the Interconnection Customer Interconnection Facilities consist of:  The Collection Station (Jointly Owned Interconnection Facilities), including:  One (1) 13.8 kV, 2500 A bus tie breaker;  Relaying;  One (1) 3Ph, 75 kVA 13800/480-277V station service transformer;  Six (6) 115 kV surge arresters;  Two (2) 25/33/41.6 MVA 115/13.8Y kV transformers;  Two (2) 13.8 kV, 2500 A breakers;  Two (2) 115 kV, 1200A, 550 kV BIL oil circuit breakers;  Two (2) 115 kV, 1200A motor operated, oil circuit breaker disconnect switches;  Two (2) 115 kV, 1200 A, motor operated line disconnect switches; and  Two (2) 115 kV, 1200 A, motor operated tie disconnect switches.  Equipment in Switchgear, including, but not limited to:  Two (2) 13.8 kV, 1200 A feeder breaker;  Six (6) 12 kV station class surge arresters;