Control Building Sample Clauses

Control Building. The Marble River Collection Substation control building shall be a pre-fabricated building complete and wired with HVAC equipment, switchboard panels, electrical and electronic equipment including lighting, receptacles, AC/DC panels, switches, overhead cable tray, conduits, grounding system, batteries, chargers, portable eyewash stations, portable fire extinguishers, exit signs, emergency lighting, security system and minimal furniture.
AutoNDA by SimpleDocs
Control Building. A stand alone control building will be provided for the Project Substation. The control building will house the relay panel, control panels, SCADA, DC Battery system, monitoring devices plus all of the support equipment, i.e. AC/DC distribution, HVAC, etc. The relay panel will contain the 34.5 kV Collector Bus and Backup Feeder Protection. The protective device will be a directional phase and ground overcurrent relay providing overall 34.5 kV bus and feeder backup protection, including over/under-frequency and overvoltage protection.
Control Building. The University, at its expense shall design and construct, or cause the design and construction of, the Control Building pursuant to Sections 5.1 and 5.2 below. Upon completion of the Control Building construction, the City will own and Maintain the Control Building pursuant to Section 8.2b below. The final decision regarding all Control Building details, including location, sizing and other requirements of the Control Building shall be determined by the City after consultation with the University; provided that, the Control Building will house the Diversion Point, pipes, valves, pumps, structures, generators and related improvements to divert Reclaimed Water to the Reclaimed Supply Lines.
Control Building. Upon completion of the Control Building construction, the City will Maintain the Control Building located on the Xxxxxxx Street Site; provided that the University, at its expense shall reimburse the City for the City’s Operating Expenses associated with the Control Building located on the Xxxxxxx Street Site, subject to Section 8.3 below.
Control Building. The control building (see attached drawing) contains power, control and commutation boards, MCC boards, operator console and battery room. Overall size of the building will be approximately 180 square meters. In addition a smaller utility building (either separate or combine together with the control building) will be constructed mainly for the air compressors Pressurized air system, provided with active carbon filter system will be provided to maintain the control building and its equipment under positive pressure to avoid H2S entrainment into the building
Control Building. All rooms' air conditioned except UPS and battery room.
Control Building. A pre-engineered metal building will be utilized. This building may be combined with the electrical building. All exterior walls shall be insulated to a minimum of R-19. The roof will be insulated to a minimum of R-30. The building will be heated and air conditioned. All windows and doors, interior and exterior, shall be metal framed. Exterior doors will be metal, insulated, and shall have reinforced half lights and will be keyed alike with knob locks and deadbolts. Outside doors shall not open directly into the control room. All windows shall be double paned with solar reflector glass. The exterior sheeting shall be 24 gauge with a color to be determined by the Company. The building interior shall be finished with a color to be determined by the Company. Floors will be linoleum tiled with a color to be determined by the Company. The ceiling will be hung with acoustic absorbing tile. Florescent lights will be hung in the ceiling. Low glare diffusers shall be used in the control room. Hot water (non potable) may be via an Instaheat under sink device. Electrical, data and phone outlets shall be provided in the control room and office. The control room will contain: • Self-closing door with a half light. • PLC Operator Interface and integral desk with power, data, and phone outlets • Fire alarm panel, turbine panel, gas monitoring panels. • PLC instrument I/O interface cabinets • other operator and plant control devices (if any) • Allocation of space for: o Two 6’ x 4’ bookshelves for plant operation manuals and project manuals. o filing cabinet o Two workstation desks for visitors, with phone, data, and power outlets. One unisex ADA (American’s with Disabilities Act)-compliant restroom will contain: • A toilet, sink, mirror, soap and towel dispenser. • mop and broom closet • mop faucet Communication closet containing: Design Criteria - RR EPC Contract, Exhibit C Rev 0 – 12/05/05 • Space for telephone switching equipment • Space for Intranet and Internet communication equipment • Dead-end runs for all voice and phone communications • Multiple outlets for communication devices • Two dedicated 120V electrical circuits for the convenience outlets The building shall also contain: • 6’ x 8’ storage room with locking door.
AutoNDA by SimpleDocs
Control Building. Bidder shall install Inverter Cum Control room near each Pond along with Transformer Yard. There is a Common control building present near the Phase-II Raw Water Pump House. This building has two parts, one part for Equipment Room for housing Switchgear, electrical equipments/panels and other part for Control Room for Control operation, office cum meeting or conference room and equipment room which is having AC environment for the operation & maintenance of entire floating Solar Plant system. In the Equipment Room only spare space has been kept for accommodating the incoming power of the individual pond power plant. Successful Bidder shall supply both 33 kV HT extension panels and 415 V LT extension panel, installation connect with the main bus and other hooking up its equipments with the existing 33 kV and 415 V Switchgear. 33 kV cable shall run from new transformer yard near each Pond (Pond no. 1, 2, and 4) to existing Common control Room near Pond No. 3.

Related to Control Building

  • Building With respect to each parcel of Real Estate, all of the buildings, structures and improvements now or hereafter located thereon. Business Day. Any day on which banking institutions located in the same city and State as the Agent’s Head Office are located are open for the transaction of banking business and, in the case of LIBOR Rate Loans, which also is a LIBOR Business Day.

  • Common Areas Tenant shall have the non-exclusive right to use in common with other tenants in the Project, and subject to the Rules and Regulations referred to in Article 5 of this Lease, those portions of the Project which are provided, from time to time, for use in common by Landlord, Tenant and any other tenants of the Project (such areas, together with such other portions of the Project designated by Landlord, in its discretion, including certain areas designated for the exclusive use of certain tenants, or to be shared by Landlord and certain tenants, are collectively referred to herein as the “Common Areas”). The Common Areas shall consist of the “Project Common Areas” and the “Building Common Areas.” The term “Project Common Areas,” as used in this Lease, shall mean the portion of the Project designated as such by Landlord or areas within the Project that the occupants of the Building are permitted to utilize pursuant to a recorded declaration and which areas shall be maintained in accordance with the declaration. The term “Building Common Areas,” as used in this Lease, shall mean the portions of the Common Areas located within the Building reasonably designated as such by Landlord. The manner in which the Common Areas are maintained and operated shall be at the reasonable discretion of Landlord and the use thereof shall be subject to the Rules and Regulations as Landlord may make from time to time. Landlord reserves the right to close temporarily, make alterations or additions to, or change the location of elements of the Project and the Common Areas, provided that, in connection therewith, Landlord shall perform such closures, alterations, additions or changes in a commercially reasonable manner and, in connection therewith, shall use commercially reasonable efforts to minimize any material interference with Tenant’s use of and access to the Premises.