II.3.10, each Controlling Technical Unit must be able to adjust its Reactive Power production or absorption automatically in the event of Grid Voltage variation at its Service Measurement Point, in accordance with the relative Sensitivity Coefficient αeq as defined in Annex 1.
Vstartup is the average Grid Voltage value of the quarter hour following the quarter hour during which the unit started up for the last time (meaning the last moment in time where the Technical Unit’s Pmeasured started to exceed its Minimum Active Power Threshold in Injection, in Offtake or in Compensator Mode (Pmin in Figure 2) as agreed in Annex 1).
In particular for the Automatic Control Service Type, he must, for the whole duration of the test, regulate his production or absorption of Reactive Power according to Grid Voltage according to requirements in Art.
MVAr’s requested are considered to be MVAr’s that are produced or absorbed when the Grid Voltage deviates from Vstartup (as defined in the present Annex).
𝛥𝑄 = − 0,45𝑥𝑃𝑛𝑜𝑚 𝛥𝐺𝑉 𝑈𝑛𝑜𝑟𝑚_𝑒𝑥𝑝𝑙 o ΔGV: the difference between the Grid Voltage before and after the network voltage variation; o ΔQ: the absolute difference between the Reactive Power measured at Qhn and the Reactive Power Measured at Qh(n-1)).