Manual Disconnect Switch Sample Clauses

Manual Disconnect Switch. 5.1 U.L.1741 Listed, inverter-based Tier 1 customer-owned renewable generation systems do not require a customer-installed manual disconnect switch.
AutoNDA by SimpleDocs
Manual Disconnect Switch. 12.01. Customer shall install a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the CRG system and any Customer wiring connected to Utility’s electric system such that back feed from the CRG system to Utility’s electric system cannot occur when the switch is in the open position. The manual disconnect switch shall be mounted separate from the meter socket on an exterior surface adjacent to the meter. The switch shall be readily accessible to Utility and capable of being locked in the open position with a Utility padlock. When locked and tagged in the open position by Utility, this switch will be under the control of Utility.
Manual Disconnect Switch. 5.1. Participant must install a manual, lockable, visible load break disconnect switch between the generation source and the Distributor’s system that is visibly marked “Participant Generation Disconnect.” The disconnect shall be mounted separate from but adjacent to the Distributor’s meter socket. The Participant shall ensure that such manual disconnect switch shall remain readily accessible to Distributor and be capable of being locked in the open position with a single Distributor utility padlock. A permanent, weatherproof single line diagram of the facility must be located adjacent to the disconnect switch. Names and current telephone numbers of at least two persons authorized to provide access to the facility that have authority to make decisions regarding the interconnection and operation of the Qualifying System will be included.
Manual Disconnect Switch. 5.1. Participant must install a manual, lockable, visible load break disconnect switch between the generation source and the Distributor’s electric power distribution system that is visibly marked “
Manual Disconnect Switch. 5.1 FPL shall require the Customer to install, at the Customer’s expense, a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the Customer-owned renewable generation and any Customer wiring connected to FPL’s system. The manual disconnect switch shall be mounted separate from, but adjacent to, the FPL meter socket. The Customer shall ensure that such manual disconnect switch shall remain readily accessible to FPL and be capable of being locked in the open position with a single FPL utility padlock.
Manual Disconnect Switch. 5.1. Participant must install an exterior manual, lockable, visible load break AC disconnect switch between the inverter and MLGW’s meter socket. For Qualifying Systems using micro-inverters, a fused AC disconnect switch must be used. (An optional DC disconnect switch is recommended between the generation source and inverter.) The AC switch must be visibly marked “
Manual Disconnect Switch. 5.1. LCEC shall require the Customer to install, at the Customer's expense, a manual disconnect switch of the visible load break type to provide a separation point between the AC power output of the Customer-owned renewable generation and any Customer wiring connected to LCEC's system. The manual disconnect switch shall be mounted separate from, but adjacent to, LCEC meter socket. The Customer shall ensure that such manual disconnect switch shall remain readily accessible to LCEC and be capable of being locked in the open position with a single LCEC utility padlock.
AutoNDA by SimpleDocs
Manual Disconnect Switch. 5.1. Participant must install a manual, lockable, visible load break disconnect switch between the generation source and the Distributor’s electric power distribution system that is visibly marked in accordance with the Distributor’s labeling requirements. The AC disconnect shall provide for dead front access. The disconnect switch shall be mounted separate from the Distributor’s meter socket in a visible location within five feet of the Distributor’s meter socket or as otherwise approved by the Distributor. Participant shall ensure that such manual disconnect switch shall remain readily accessible to Distributor and be capable of being locked in the open position by the Distributor with a single utility padlock.
Manual Disconnect Switch. Participant must install a manual, lockable, visible load break disconnect switch between the Qualifying System and GEA’s system marked “Participant Generation Disconnect”. This disconnect shall be mounted separate from, but adjacent to, GEA’s meter socket. The participant shall ensure that such manual disconnect switch shall remain readily accessible to GEA and be capable of being locked in the open position with a single GEA utility padlock. A permanent, weatherproof single line diagram of the facility must be located adjacent to the disconnect switch. Names and current telephone numbers of at least two persons authorized to provide access to the facility that have authority to make decisions regarding the interconnection and operation of the Qualifying System will be included.
Manual Disconnect Switch. 5.1. Participant must install a manual, lockable, visible load break disconnect switch between the generation source and AEC’s system that is visibly marked “Participant Generation Disconnect”. The disconnect shall be mounted separate from but in proximity to the members meter socket. The Participant shall ensure that such manual disconnect switch shall remain readily accessible to AEC and be capable of being locked in the open position with a single AEC utility padlock.