Voltage Transformers Requirements Sample Clauses

Voltage Transformers Requirements. Each metering point shall have a dedicated set of metering class of voltage transformers. Unless otherwise agreed upon by the Parties, all metering shall be type 3.0 element metering, and have three (3) metering accuracy voltage transformers. Voltage transformers shall meet or exceed an accuracy class of 0.3% (as defined in IEEE C57.13). The secondary of the voltage transformer shall be exclusively used for the revenue meters only, so as not to exceed the secondary burden of the stated voltage transformer’s name plate burden rating provided, however, that voltage transformers with two secondary windings, may have one winding dedicated to the revenue meters, and the other winding used for relaying purposes or for other station metering. The nameplate burden rating on either winding must not be exceeded. Voltage transformers shall comply with the minimum BIL rating as specified in standards IEEE C57.13 and ANSI C12.11.
AutoNDA by SimpleDocs
Voltage Transformers Requirements. Each metering point shall have metering class voltage transformers. Unless otherwise agreed upon by the Parties, all metering shall be type 3.0 element metering, and have three (3) metering accuracy voltage transformers. Voltage transformers should meet or exceed an accuracy class of 0.3% (as defined in IEEE C57.13). The 115 volt secondary of the voltage transformer shall be exclusively used for the revenue meters only, so as not to exceed the secondary burden of the stated voltage transformer’s name plate burden rating.

Related to Voltage Transformers Requirements

  • Software Requirements 7 Developer shall prepare the Project Schedule using Oracle’s Primavera P6.

  • Access Requirements You will be responsible for providing the System to enable you to use an Electronic Service.

  • Support Requirements If there is a dispute between the awarded vendor and TIPS Member, TIPS or its representatives may assist, at TIPS sole discretion, in conflict resolution or third party (mandatory mediation), if requested by either party. TIPS, or its representatives, reserves the right to inspect any project and audit the awarded vendors TIPS project files, documentation and correspondence. Status of TIPS Members as Related to This Agreement TIPS Members stand in the place of TIPS as related to this agreement and have the same access to the proposal information and all related documents. TIPS Members have all the same rights under the awarded Agreement as TIPS.

  • Required Coverages For Generation Resources Of 20 Megawatts Or Less Each Constructing Entity shall maintain the types of insurance as described in section 11.1 paragraphs (a) through (e) above in an amount sufficient to insure against all reasonably foreseeable direct liabilities given the size and nature of the generating equipment being interconnected, the interconnection itself, and the characteristics of the system to which the interconnection is made. Additional insurance may be required by the Interconnection Customer, as a function of owning and operating a Generating Facility. All insurance shall be procured from insurance companies rated “A-,” VII or better by AM Best and authorized to do business in a state or states in which the Interconnection Facilities are located. Failure to maintain required insurance shall be a Breach of the Interconnection Construction Service Agreement.

  • Technical and Interconnection Requirements 2.1 Consumer agrees that his Rooftop Solar PV System and Net Metering System will conform to the standards and requirements specified in the Policy, Regulations and Supply Code as amended from time to time.

Time is Money Join Law Insider Premium to draft better contracts faster.