Transmission System. The facilities controlled or operated by the Transmission Provider or the Transmission Owner that are used to provide transmission service under the Tariff. Upgrades – The required additions and modifications to the Transmission Provider’s Transmission System at or beyond the Point of Interconnection. Upgrades may be Network Upgrades or Distribution Upgrades. Upgrades do not include Interconnection Facilities. Attachment 2 Description and Costs of the Small Generating Facility, Interconnection Facilities, and Metering Equipment The Project is a proposed 1.426 MW farm waste generation facility located at 0000 Xxxxxx Xxxx in Wyoming County, New York, and interconnecting to the NG-NM 13.2 KV Feeder #2951, via a four hundred foot underground service lateral. The DEVELOPER is indicating that its total on-property load will remain at 300 KW. The Developer has not yet established a proposed In Service Date1; Initial Synchronization Date2; nor expected Commercial Operation Date3 for this Project. 4 The Synergy LLC dairy farm currently takes 277/480 Volt service from a 750 KVA pad fed underground from pole 21-1 that will be removed upon final energization of the proposed generator and GSU station. The Project is to consist of one (1) 480 V STAMFORD GENERATOR, Type: PE 734 E2 with Type rating of 2300 KVA and a rated output of 1426 KW at 100 % pf and 1416 KW at 80% pf. The generator’s reactive power capability is listed as 0.8 to 1.0 lagging.