Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line diagram in Attachment 3, the ICIF consist of the following:
Appears in 9 contracts
Samples: Service Agreement, Service Agreement, Interconnection Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:
Appears in 8 contracts
Samples: Service Agreement, Service Agreement, Interconnection Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:
Appears in 4 contracts
Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:
Appears in 4 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be SERVICE AGREEMENT NO. 2572 located on property owned or leased by the Interconnection Customer. As depicted on the one- line oneline diagram in Attachment 3, the ICIF consist of the following:
Appears in 4 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line oneline diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2571
Appears in 4 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2638
Appears in 3 contracts
Samples: Service Agreement, Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF Interconnection Customer’s Interconnection Facilities will be located on property owned or leased by the Interconnection Customer. As , and, as depicted on the one- line diagram in Figure 1 in Attachment 3, the ICIF will consist of the following:following major electrical and physical equipment: SERVICE AGREEMENT NO. 2576
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment RTU described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2662
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
Interconnection Customer’s Interconnection Facilities. The As depicted on the one-line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line diagram in Attachment 3, the ICIF consist of the following:.
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2608
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2666
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF Interconnection Customer’s Interconnection Facilities will be located on property owned or leased by the Interconnection Customer. As , and, as depicted on the one- line diagram in Figure 1 in Attachment 3, the ICIF will consist of the followingfollowing major electrical and physical equipment:
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The As depicted on the one-line diagram in Attachment 3, the Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection CustomerSERVICE AGREEMENT NO. As depicted on the one- line diagram in Attachment 3, the ICIF consist of the following:2673
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line oneline diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2574
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) and the Small Generating Facility, except the Connecting Transmission Owner-owned metering and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- line oneline diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2573
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIFICIFs”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned metering metering, remote terminal unit (“RTU”), and telecommunications equipment described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF ICIFs consist of the following:: SERVICE AGREEMENT NO. 2756
Appears in 1 contract
Samples: Service Agreement
Interconnection Customer’s Interconnection Facilities. The Interconnection Customer’s Interconnection Facilities (“ICIF”) include all of the facilities between the Interconnection Customer’s side of the Point of Change of Ownership (“PCO”) PCO and the Small Generating Facility, except the Connecting Transmission Owner-owned revenue metering and telecommunications equipment remote terminal unit (“RTU”) described in Section C below. The ICIF will be located on property owned or leased by the Interconnection Customer. As depicted on the one- one-line diagram in Attachment 3, the ICIF consist of the following:: SERVICE AGREEMENT NO. 2777
Appears in 1 contract
Samples: Service Agreement