Deemed Commissioning Sample Clauses

Deemed Commissioning. In the event that JPS does not accept energy produced by the Facility during the scheduled Commissioning of the Facility in breach of this Agreement (and, for avoidance of doubt, expressly excluding JPS’ inability or refusal to accept such energy due to the occurrence of an event of Force Majeure, an Emergency or a Company Event of Default), and as a result the Commissioning of the Facility is delayed for more than fourteen (14) Days from the scheduled date, then, pending actual testing and upon receipt of a certificate from the Independent Engineer to the effect that the Facility is ready for testing and Commissioning, the Facility shall be deemed to be providing Dependable Capacity equivalent to [input MEGAWATTS] MW for the purposes of Fixed Payments to be made by JPS pursuant to Clause 9.1 hereof provided that,
AutoNDA by SimpleDocs
Deemed Commissioning. In the event that for any reason (other than a breach by Project Company of its obligations under this Agreement or any other Project Agreement): Due to (A) any action or inaction by GPA which is inconsistent with the terms of this Agreement (including any default or breach), [(B) the discovery of a Pre-Existing Site Condition, (C) any failure by GPA or any third party appointed by GPA to carry out remediation work in accordance with Article 6.6.1(c)] or (D) unavailability of Fuel, a Commercial Operation Test is delayed beyond the date falling fourteen (14) Days before the Required Phase 1 Commercial Operation Date or Required Phase 2 Commercial Operation date (whichever is applicable), then upon receipt of a certificate from an Independent Engineer to the effect that the Facility is, or would have been, ready for testing by the relevant Required Commercial Operation Date, the Facility shall be deemed Commissioned for the respective Phase fifteen (15) Days after the relevant Required Commercial Operation Date (provided that for the avoidance of doubt the Project Company shall in no event be required to pay delay liquidated damages under Article 9.1 for such fifteen (15) Day period) and the Facility shall be deemed to be providing Initial Dependable Capacity equal to the applicable Contracted Facility Capacity for the purposes of payments of Capacity Charges to be made by GPA to Project Company. If the Facility has been deemed Commissioned for a Phase, the Commercial Operation Tests for such phase shall be conducted at the first available opportunity after such deemed Commissioning, and the Initial Dependable Capacity adjusted as a result of such test in accordance with subsection (b) below. Project Company shall use reasonable efforts to mitigate the delay caused by any of the events mentioned in this Article 8.5.1(a). In the event that the Initial Dependable Capacity of the Facility at the Commercial Operation Tests after the Phase has been deemed Commissioned, is less than the applicable Contracted Facility Capacity, Project Company shall refund to GPA an amount equal to: the difference, if any, between the applicable Contracted Facility Capacity and the Initial Dependable Capacity divided by the applicable Contracted Facility Capacity; times the total Capacity Charges paid between the date of deemed Commissioning and the date upon which the Initial Dependable Capacity Tests take place; provided, however, that in the event that the Initial Dependable Cap...
Deemed Commissioning. (a) In the event that for any reason (other than a breach by Project Company of its obligations under this Agreement or any other Project Agreement):
Deemed Commissioning. 6.3.1 If [(a)] any Unit has been synchronised (or the Engineer has certified that any Unit is ready to be synchronised) [and (b) the Related Infrastructure has been certified by the Engineer to be ready for its Commissioning Test], and [in either case] the Commissioning Test thereof is delayed because of:
Deemed Commissioning. In the event that GPL does not accept energy produced by the Facility during the scheduled Commissioning of the Facility in breach of this Agreement (and, for avoidance of doubt, expressly excluding GPL’s inability or refusal to accept such energy due to the occurrence of an event of Force Majeure, an Emergency or a Company Event of Default), and as a result the Commissioning of the Facility is delayed for more than fourteen (14) Days from the scheduled date, then, pending actual testing and upon receipt of a certificate from the Independent Engineer to the effect that the Facility is ready for testing and Commissioning, the Facility shall be deemed to be providing Dependable Capacity equivalent to [input MEGAWATTS] MW for the purposes of Fixed Payments to be made by GPL pursuant to Clause 9.1.
Deemed Commissioning. If the Commercial Operation Date is delayed or prevented beyond the Commercial Operation Longstop Date by any of the following events: Governmental Force Majeure; failure by the Buyer to perform any of its obligations under this Agreement; or failure by Network Operator to make the Grid available and/or to evacuate Energy generated (or to be generated) during Initial Tests carried out (or to be carried out) in accordance with this Agreement, the Project Company shall be entitled to apply in writing to the Engineer (with a copy provided to the Buyer) for a certification of the date on which, in the Engineer's professional opinion, the Commercial Operation Date would have occurred but for the occurrence of the event(s) listed above (such date the "Deemed Commercial Operation Date").
Deemed Commissioning. In the event that JPS does not accept energy produced by the Facility during the scheduled Commissioning of the Facility in breach of this Agreement (and, for avoidance of doubt, expressly excluding JPS’ inability or refusal to accept such energy due to the occurrence of an event of Force Majeure, an Emergency or a Company Event of Default), and as a result the Commissioning of the Facility is delayed for more than fourteen (14) Days from the scheduled date, then, pending actual testing and upon receipt of a certificate from the Independent Engineer to the effect that the Facility is ready for testing and Commissioning, the Facility shall be deemed to be providing Dependable Capacity equivalent to [input MEGAWATTS] MW for the purposes of Fixed Payments to be made by JPS pursuant to Clause 9.1 hereof provided that, (a) the Company shall not be liable for the payment of liquidated damages in accordance with Clause 9.4.1 for the number of days equivalent to the period commencing on the Day the Facility was deemed Commissioned in accordance with this Clause 4.5 and ending on the earlier of
AutoNDA by SimpleDocs
Deemed Commissioning. (a) If the BOT Company is unable to conduct or complete testing of the First Unit or the Facility in order to Commission the First Unit or the Facility in accordance with the schedule of tests provided by the BOT Company pursuant to Article 7.1 due to:
Deemed Commissioning a) If the Seller would have been able to achieve the Commissioning Date but for reasons of Force Majeure, failure of the Buyer or any Governmental Authority to:

Related to Deemed Commissioning

  • Commissioning Commissioning tests of the Interconnection Customer's installed equipment shall be performed pursuant to applicable codes and standards. If the Interconnection Customer is not proceeding under Section 2.3.2, the Utility must be given at least ten (10) Business Days written notice, or as otherwise mutually agreed to by the Parties, of the tests and may be present to witness the commissioning tests.

  • TESTING AND COMMISSIONING 24 Allow for a Lump Sum for testing and commissioning of the entire electrical installation, including the provision of Compliance Certificate. Item Carried to Collection R Section No. 4 Electrical Installation (Provisional) Bill No. 1 Electrical Installation COLLECTION Total Brought Forward from Page No. Carried to Final Summary 76 77 R Amount FINAL SUMMARY Section No Page No 1 Preliminaries 26 2 Alterations (Provisional) 30 3 External Works (Provisional) 73

  • Synchronization, Commissioning and Commercial Operation 4.1.1 The Power Producer shall give at least thirty (30) days written notice to the SLDC and GUVNL, of the date on which it intends to synchronize the Power Project to the Grid System.

  • Contract Completion The Contractor shall achieve Contract Completion, as the term is defined in this Agreement, within 60 calendar days of Substantial Completion.

  • Decommissioning The expenditure for Decommissioning will be estimated on the basis of technical studies undertaken by the Contractor, to be agreed by the National Petroleum Agency, as part of each Field Development Program and revised as necessary.

  • Project Completion Part 1 – Material Completion

  • Operation Delays STATE shall have the authority to delay or suspend the operations of PURCHASER and contractors of PURCHASER, wholly or in part, under this contract for such period or periods necessary due to fire hazard conditions, severe weather occurrence, surveying for threatened or endangered species listed under the state or federal Endangered Species Act, or any other activity STATE determines to be necessary for identification, management, or protection of a threatened or endangered species. PURCHASER agrees to cooperate with surveying efforts of STATE or its contractors. In no event shall STATE be liable for any costs incurred by PURCHASER by reason of delay or suspension under this section, including but not limited to costs of additional move-in/move-out of equipment and personnel, extra fire and equipment security, and insurance or bonding expenses.

  • Planned Outages Seller shall schedule Planned Outages for the Project in accordance with Good Industry Practices and with the prior written consent of Buyer, which consent may not be unreasonably withheld or conditioned. The Parties acknowledge that in all circumstances, Good Industry Practices shall dictate when Planned Outages should occur. Seller shall notify Buyer of its proposed Planned Outage schedule for the Project for the following calendar year by submitting a written Planned Outage schedule no later than October 1st of each year during the Delivery Term. The Planned Outage schedule is subject to Buyer’s approval, which approval may not be unreasonably withheld or conditioned. Buyer shall promptly respond with its approval or with reasonable modifications to the Planned Outage schedule and Seller shall use its best efforts in accordance with Good Industry Practices to accommodate Xxxxx’s requested modifications. Notwithstanding the submission of the Planned Outage schedule described above, Seller shall also submit a completed Outage Notification Form to Buyer no later than fourteen (14) days prior to each Planned Outage and all appropriate outage information or requests to the CAISO in accordance with the CAISO Tariff. Seller shall contact Buyer with any requested changes to the Planned Outage schedule if Seller believes the Project must be shut down to conduct maintenance that cannot be delayed until the next scheduled Planned Outage consistent with Good Industry Practices. Seller shall not change its Planned Outage schedule without Buyer’s approval, not to be unreasonably withheld or conditioned. Seller shall use its best efforts in accordance with Good Industry Practices not to schedule Planned Outages during the months of July, August, September and October. At Buyer’s request, Seller shall use commercially reasonable efforts to reschedule Planned Outage so that it may deliver Product during CAISO declared or threatened emergency periods. Seller shall not substitute Energy from any other source for the output of the Project during a Planned Outage.

  • Downtime Due to the nature of server provision, downtime and lost transmissions may occur as part of routine maintenance. You are advised to maintain a copy of your account status and details of Content purchased.

  • Utilization Scale STATE shall scale logs or portions of logs that are broken, wasted, or not removed by PURCHASER due to: (1) improper felling or bucking of the logs; (2) failure to remove the logs prior to deterioration; and (3) logs remaining on the timber sale area after completion of logging, provided the logs were merchantable prior to breakage or wastage. Material used to meet down material requirements in the section titled, "Reserved Timber," shall not be considered for utilization scale. PURCHASER shall pay for the logs at the contract price designated in Section 44. STATE shall notify PURCHASER of the volume of logs so scaled. Payment shall be considered due on such volume as if the logs were removed on the date of said notification. In the event PURCHASER disagrees with the findings made by STATE under this section, PURCHASER may furnish scaling by a third-party scaling organization acceptable to STATE. Costs and expenses of such third party shall be paid for by PURCHASER, and the findings of the third party shall be final.