Control Equipment. Subject to final approval by Buyer as of the date of final execution of the Interconnection Agreement, the following control equipment shall be installed at the Facility: A Power Plant Controller (PPC) which includes all features required to comply with this Agreement and the Interconnection Agreement, including, but not limited to, active power control (dispatch), power factor set point control, voltage schedule set point control, active power ramp rates, and frequency response control (from regulation signal sent from System Operator). Set points such as active power control, as required by this Agreement, will be made available to Buyer via a hard-wired DNP3 path at the Facility’s Point of Interconnection. Remote access to the Facility’s HMI (the Plant Controller Interface) will be given for control of the required variables, by the Buyer