Examples of Powerlink Assets in a sentence
Chapter 7, "Hearings," in this Management Directive discusses more fully this provision.
Where Powerlink exercises its right to disconnect under clause 8.1 (“Emergency disconnection”), 8.3 (“Disconnection for Technical Breach”), 8.4 (“Disconnection for financial breach ”) it must reconnect the Powerlink Assets and the Negotiated Assets (as applicable) as soon as reasonably practicable after the condition leading to the disconnection has ended and all matters relevant to the exercise of the right of disconnection have been rectified to Powerlink’s reasonable satisfaction.
See Adviser Business Continuity and Transition Plans, Advisers Act Rel.
Schedule 1 – Powerlink Assets 1 Transmission Network Connection Point The Transmission Network Connection Point (TNCP) is identified in the Connection Schematic Diagrams (Diagram 1) of this Schedule 1 (“Powerlink Assets”), item 4 (“Connection Schematic Diagrams”).
Where Powerlink exercises its right to disconnect under clause 18.1 it must reconnect the Powerlink Assets as soon as reasonably practicable after the condition leading to the disconnection has ended and all matters relevant to the exercise of the right of disconnection have been rectified to Powerlink’s reasonable satisfaction.
If Powerlink reasonably believes that the operation of the Customer Facility, or any part of it, poses a threat to Power System Security or may lead to damage to the Transmission Network or any of the Powerlink Assets, Powerlink may take any action that it reasonably considers necessary (including disconnection at the Asset Boundary) to maintain Power System Security or to avoid damage to the Transmission Network or the Powerlink Assets without giving prior notice.
Powerlink may inspect and test the Customer Facility (or any relevant part of it) to verify that a Technical Breach has been remedied or that a threat to the Powerlink Assets or Power System Security will not recur if it reasonably considers that verification is necessary.
The Asset Boundary between the Powerlink Assets and the Generator’s Facility for the primary system (xxx kV) is identified in item 4 (“Connection Schematic Diagrams”) of this Schedule 1 (“Powerlink Assets”).
Powerlink is not obliged to reconnect the Powerlink Assets and the Negotiated Assets (as applicable) or the Generator Facility where it has refused to connect or has disconnected under this clause 8 (“Disconnection or refusal to connect”) unless the Generator has remedied the Technical Breach or taken steps to avoid the recurrence of the threat to the Powerlink Assets and the Negotiated Assets (as applicable) or Power System Security to Powerlink’s reasonable satisfaction.
Powerlink is not obliged to commission the Powerlink Works, connect or reconnect the Powerlink Assets or the Generator Facility where it has refused to connect or has disconnected under this clause 7 (“Disconnection or refusal to connect”) unless the Generator has remedied the Technical Breach or taken steps to avoid the recurrence of the threat to the Powerlink Assets or Power System Security to Powerlink’s reasonable satisfaction.