Telecommunications Circuit Sample Clauses

Telecommunications Circuit. A new fiber facility will be required at the Xxxxxxxxx Solar Collector Substation for protection systems and data transmittal and will include: • one (1) DS1 circuit from the Xxxxxxxxx Solar Collector Substation to Connecting Transmission Owner’s Schaghticoke Substation; • one (1) DS1 circuit from the Xxxxxxxxx Solar Collector Substation to Connecting Transmission Owner’s Battenkill Substation; and • one (1) T1 multiprotocol label switching (“MPLS”) circuit for the energy management system and remote terminal unit (“EMS-RTU”).
AutoNDA by SimpleDocs
Telecommunications Circuit. A new Telco fiber facility will be required at the North Country Solar Collector Station for protection systems and data transmittal. The new fiber facility shall provide:
Telecommunications Circuit. The Interconnection Customer shall install a single mode, all-dielectric self-supporting (“ADSS”), 24 strand fiber optic cable between the Xxxxxxx Road Collector Substation control house and the Point of Change of Ownership. A new fiber facility will be required at the Xxxxxxx Road Collector Substation. The following telecommunications will be required on the new fiber facility: • one (1) DS1 MPLS virtual private network (“VPN”) circuit for the energy management system and report transmitting unit (“EMS-RTU”); and • one (1) plain old telephone (“POTs”) line for station voice communication.
Telecommunications Circuit. A new fiber facility will be required at the Albany 1 Collector Substation for protection systems and data transmittal. The new fiber facility shall provide: • one (1) DS1 circuit from the Albany 1 Collector Substation to Long Lane Substation; • one (1) DS1 circuit from the Albany 1 Collector Substation to LaFarge Substation; • one (1) DS1 multiprotocol label switching (“MPLS”) virtual private network (“VPN”) circuit for the energy management system and report transmitting unit (“EMS-RTU”); and • one (1) plain old telephone service (“POTs”) line for station voice communication.
Telecommunications Circuit. A new Telco fiber facility will be required at the Grissom Solar Collector Substation for protection systems and data transmittal. The new fiber facility shall provide: • one (1) DS1 circuit from the Grissom Solar Collector Substation to Connecting Transmission Owner’s Florida Substation for the DTT; • one (1) DS1 circuit from the Grissom Solar Collector Substation to Connecting Transmission Owner’s Ephratah Substation for the DTT; • one (1) T1 MPLS for energy management system and report transmitting unit (“EMS- RTU”); and • one (1) plain old telephone service (“POTs”) line for station voice communication.
Telecommunications Circuit. A new Telco fiber facility will be required at the Hilltop Solar Collector Station for protection systems and data transmittal. The new fiber facility shall provide: • one (1) DS1 circuit from the Hilltop Solar Collector Station to the Schaghticoke Substation; • one (1) DS1 circuit from the Hilltop Solar Collector Station to the Eastover Substation; • one (1) plain old telephone service (“POTs”) line; and • one (1) T1 MPLS circuit for energy management system-remote terminal unit (“EMS- RTU”). The Interconnection Customer is responsible for ordering the fiber facility required at the Hilltop Solar Collector Substation and provisioning the T1 MPLS circuit. The Connecting Transmission Owner will provision the Verizon DS1 circuits from Hilltop Solar Collector Substation to the Schaghticoke and Eastover Substations. (Note: Verizon may retire T1 services in the future. If T1 circuits are not available at the time of project implementation, alternative technologies will be required which could change the overall cost of the telecom solution.) To the extent the Small Generating Facility feeder lines, communication circuits, access roads, and/or driveways cross Connecting Transmission Owner-owned transmission or distribution circuits, such crossings must be reviewed by the Connecting Transmission Owner in accordance with the Connecting Transmission Owner’s land use requirements. Per the Project Specific Specifications (defined below), feeder line crossings shall be underground so as to maintain the reliability of service provided by the Connecting Transmission Owner to other customers via the impacted transmission and distribution facilities.
Telecommunications Circuit. The Company shall have sole responsibility for providing, installing, and commissioning all the facilities and equipment for telemetering, communication, control, and monitoring, including voice channels, which may be required for the Facility to interface with DPDC SCADA System, including any RTU(s) within the Facility.
AutoNDA by SimpleDocs
Telecommunications Circuit. The Sky High Solar Collector Substation will include a new Verizon fiber facility that shall provide: • one (1) DS1 circuit from the Sky High Solar Collector Substation to the Xxxxxx Substation; • one (1) DS1 circuit from the Sky High Solar Collector Substation to the Cortland Substation; • one (1) DS1 circuit from the Sky High Solar Collector Substation to Connecting Transmission Owner’s Syracuse office complex to support teleprotection; • one (1) DS1 multiprotocol label switching and virtual private network (“MPLS VPN”) circuit for emergency management system-remote telemetry unit (“EMS-RTU”); and • one (1) plain old telephone service (“POTs”) line for station voice communication.
Telecommunications Circuit. For Generator Tie Line protection, DTT, and data transmittal, the Developer will install two (2) 24-strand, 1300 nm, single mode, fiber optic communication cables between the Ball Hill Collector Substation and the Xxxxxxxx Road Station. Connecting Transmission Owner standards require that the primary and secondary protection telecom circuits be physically separate and fully independent of each other. The Developer shall provide a DNP protocol enabled port on the RTU at the Ball Hill Collector Substation. The Developer’s RTU at the Ball Hill Collector Station shall connect at Xxxxxxxx Road Station to a RS-232 serial port on the GarrettCom DX- 940, or one of the RTUs, via the Developer’s fiber line between the two stations.
Telecommunications Circuit. The Interconnection Customer will be responsible for bringing a new fiber facility from the local carrier into the Flat Hill Solar Collector Substation. The Interconnection Customer shall: • install a dedicated 4’x8’x3/4” fire retardant backboard for cable termination and local carrier equipment installation; • construct two (2) 4” Schedule 80 conduits from the meet point outside the Flat Hill Solar Collector Substation into the control house (if required by the local carrier) for telecom cable placement; and • provide a dedicated DC power rack, which will contain a DC/DC converter system to convert 125 VDC station battery to -48 VDC. The rack will also contain a 125 VDC to 120 VAC inverter. DC Power rack output will support the telco fiber multiplex equipment. The Interconnection Customer is responsible for ordering the fiber facility required at the Flat Hill Solar Collector Substation and ordering one (1) Verizon multiprotocol label switching (“MPLS”) T1/128K circuit or 10Mb/s ethernet for supervisory control and data acquisition (“SCADA”)/RTU. Once the fiber facility has been installed at the Flat Hill Solar Collector Substation and the Interconnection Customer has completed all make ready work in accordance with the Project Specific Specifications (as defined below), the Connecting Transmission Owner will order the point-to-point tele-protection circuits between the Flat Hill Solar Collector Substation and the remote Inghams and Valley Substations. (Note: Verizon may retire T1 services in the future. If T1 circuits are not available at the time of project implementation, alternative technologies will be required which could change the overall cost of the telecom solution.) To the extent the Small Generating Facility’s feeder lines, communication circuits, access roads, and/or driveways cross Connecting Transmission Owner-owned transmission or distribution circuits, such crossings must be reviewed by the Connecting Transmission Owner in accordance with the Land Use Application and Requirements included in Appendix F to the Facilities Study for the Small Generating Facility. Per the Project Specific Specifications (as SERVICE AGREEMENT NO. 2777 defined below), feeder line crossings shall be underground so as to maintain the reliability of service provided by the Connecting Transmission Owner to other customers via the impacted transmission and distribution facilities.