System Protection Requirements. a) Line 6 Direct transfer trip (“DTT”) will be used between the Fairway Solar Collector Substation and the line terminals at Connecting Transmission Owner’s Corning and XxXxxxxx Substations to ensure removal of the generation. This will require the installation of two (2) XXX XXXX0000 tele- protection sets or an IMUX with DS-TT cards at the Fairway Solar Collector Substation. The Connecting Transmission Owner will provide details on the communication model numbers during detailed design. The Interconnection Customer is to provide redundant 115kV line protection to remove the generation for line faults. Two sets of C800 multi-ratio current transformers (“CT”) shall be provided for these schemes.
Appears in 2 contracts
Samples: Service Agreement, Service Agreement
System Protection Requirements. a) Line 6 Direct transfer trip (“DTT”) will be used between the Fairway Solar Collector Substation and the line terminals at Connecting Transmission Owner’s Corning and XxXxxxxx Substations to ensure removal of the generation. This will require the installation of two (2) XXX XXXX0000 tele- RFL GARD8000 tele-protection sets or an IMUX with DS-TT cards at the Fairway Solar Collector Substation. The Connecting Transmission Owner will provide details on the communication model numbers during detailed design. The Interconnection Customer is to provide redundant 115kV line protection to remove the generation for line faults. Two sets of C800 multi-ratio current transformers (“CT”) shall be provided for these schemes.
Appears in 1 contract
Samples: Service Agreement
System Protection Requirements. a) Line 6 5 Direct transfer trip (“DTT”) will be used between the Fairway Hawthorn Solar Collector Substation and the line terminals at the Connecting Transmission Owner’s Corning North Xxxx and XxXxxxxx Hoosick Substations to ensure removal of the generation. This will require the installation of two (2) XXX XXXX0000 tele- RFL GARDPro tele-protection sets or an IMUX with DS-TT cards at the Fairway Hawthorn Solar Collector Substation. The Connecting Transmission Owner will provide details on the communication GARDPro model numbers number with the Connecting Transmission Owner’s logic during detailed engineering design. The Interconnection Customer is to will provide redundant 115kV line protection to remove the generation for line faults. Two sets of C800 multi-ratio current transformers (“CTCTs”) shall be provided for these schemes.
Appears in 1 contract
Samples: Service Agreement