Synchronous and Induction Generation Sample Clauses

Synchronous and Induction Generation. Capacity less than 100 KVA 5.5.1 Full Load Rejection - The customer's generation facility must be designed with the capability or protection to withstand sudden loss of load. 5.5.2 De-energized SPPCo Circuit - Electrical relays must be provided to prevent the customer's generator from being connected parallel to SPPCo's system if SPPCo's system is de-energized.
Synchronous and Induction Generation. Capacity 100 KVA - 1000 KVA The requirements described in section 5.0 also apply to 100 KVA to 1000 KVA generation.
Synchronous and Induction Generation. Capacity 100 KVA - 1000 KVA The requirements described in section 5.0 also apply to 100 KVA to 1000 KVA generation. 6.1 Overfrequency Protection - Overfrequency in addition to underfrequency protection is required. Frequency protection shall not have time delay. 6.2 Power Factor Correction - Power factor correction could be required at SPPCo's option on induction generators greater than 100 KVA.