Common use of Security Systems Clause in Contracts

Security Systems. The building has a security and access control system installed that would require connectivity to the BMS. For access control, Impro seems to be the preferred installer for the access control, systems. Most impro systems can be connected to the bms but remains the responsibility of the contractor to confirm this during detail design and installation. Fire Detection: There is a Fire Detection system installed in the building for the whole site. The main fire panel is a Ziton addressable fire panel that is not connected to a BMS system. Depending on the communication port fitted within the panel, an upgrade maybe required that a BMS interface card be installed for connectivity to the BMS. If the panel already has a TCP/IP port, then no upgrade is required. Server Room: There is a server room in this building already connected to a network. The BMS installation would run on the already existing network. UPS: There is a UPS installed in the server room. The UPS would have to be incorporated into the building management system. Geyser: Not installed. Ground Water Systems: There is a sump pump installed for the ground water. This pump would require connectivity to a BMS for water flooding monitoring and control. Building 10: This building does not have a BMS installed. The following equipment is installed: Mains Incomer The building is fed from the main substation located at Building 8. The mains circuit breaker is not BMS compatible and would require an upgrade for BMS compatibility. HVAC Systems: The HVAC system at building 10 consists mainly of split units installed in the offices known as (window shakers). These are mostly manufactured by Mitsubishi. They would require an upgrade for BMS connectivity. A heat pump was also observed during the site assessment. The HVAC equipment is currently not connected to a BMS system. Lifts: This building does not have a lift installed. Generator: This building is fed from the generator that is located at building 8. Lighting The lighting is mostly comprised of fluorescent type of light fittings, both surface and recess mounted. The light fittings would require replacement to have control switchgear that can be connected to a control panel that would be monitored by the BMS. Water Meter: The water meter is manufactured by Sensus and is fitted with a High Resolution Interface (HRI) pulse and data device that can be connected to a pulse data logger for connectivity to a BMS. The water meter usage is currently being monitored by Zednet Water Monitoring Solutions company. Energy Meters: The mains incomer for the building is located at the main substation. The mains incomer is fitted with a Xxxxxxxxx Electrical meter PM3250 which is fitted with a 37 modbus communication protocol. From discussions with personnel on site, it would seem the meters are remotely monitored/connected from the Muckleneuk campus. Water Harvesting: The building has a rainwater harvesting system installed that would require connectivity to a BMS.

Appears in 1 contract

Samples: www.unisa.ac.za

AutoNDA by SimpleDocs

Security Systems. The building has a security and access control system installed that would require connectivity to the BMS. This includes CCTV. For access control, Impro seems to be the preferred installer for the access control, systems. Most impro systems can be connected to the bms but remains the responsibility of the contractor to confirm this during detail design and installation. Fire Detection: There is a Fire Detection system installed in the building for the whole site. The main fire panel is a Ziton addressable fire panel that is not connected to a BMS system. Depending on the communication port fitted within the panel, an upgrade maybe required that a BMS interface card be installed for connectivity to the BMS. If the panel already has a TCP/IP port, then no upgrade is required. Server Room: There is a server room in this building already connected to a network. The BMS installation would run on the already existing network. UPS: There is a UPS installed in the server room. The UPS would have to be incorporated into the building management system. Geyser: Not installed. Ground Water Systems: There is a sump pump installed for the ground waterNot Installed. This pump would require connectivity to a BMS for water flooding monitoring and control. Building 10Xxxx Xxxxxxxxx: This building is quite new with modern systems for energy monitoring installed. It does not have a BMS installed. The extent of what the BMS monitors and controls would have to be verified during the detailed site inspection. The following equipment is installed: Mains Incomer The building is fed from a minisubstation that is installed externally to the main substation located at Building 8building. The mains circuit breaker is not BMS compatible and would require an upgrade for BMS compatibility. HVAC Systems: This building has several HVAC systems installed comprising: • Chiller plants • Air handling Units • Split units The HVAC system at building 10 consists mainly of split chiller plants and air handling units installed in the offices known as (window shakers). These are mostly manufactured by Mitsubishi. They would require an upgrade for have their own BMS connectivity. A heat pump was also observed during the site assessment. The HVAC equipment is currently not connected BMS would have to a BMS system. Lifts: This building does not have a lift installed. Generator: This building is fed from the generator that is located at building 8. Lighting The lighting is mostly comprised of fluorescent type of light fittings, both surface and recess mounted. The light fittings would require replacement be configured to have control switchgear that can be able to be connected to a control panel new BMS system installation for the entire building if required. The HVAC system has a dedicated generator that would be monitored by the BMS. Water Meter: The water meter is manufactured by Sensus and is fitted with a High Resolution Interface (HRI) pulse and data device that can be connected to a pulse data logger for connectivity to a BMS. The water meter usage is currently being monitored by Zednet Water Monitoring Solutions company. Energy Meters: The mains incomer for the building is located at the main substation. The mains incomer is fitted with a Xxxxxxxxx Electrical meter PM3250 which is fitted with a 37 modbus communication protocol. From discussions with personnel on site, it would seem the meters are remotely monitored/connected from the Muckleneuk campus. Water Harvesting: The building has a rainwater harvesting system installed that would also require connectivity to a BMSBMS monitoring.

Appears in 1 contract

Samples: www.unisa.ac.za

Security Systems. The building has buildings have a security and access control system installed that would require connectivity to the BMS. For access control, Impro seems to be the preferred installer for the access control, systemsThis includes CCTV. Most impro systems can be connected to the bms but It remains the responsibility of the BMS contractor to confirm this connectivity of the security systems to a BMS during detail design and installation. Fire Detection: There is a Fire Detection system installed in the building for the whole on site. The main fire panel is a Ziton addressable fire panel that is not connected to a BMS system. Depending on the communication port fitted within the panel, an upgrade maybe required that a BMS interface card be installed for connectivity to the BMS. If the panel already has a TCP/IP port, then no upgrade is required. Server Room: There is a server room in this building already connected to a network. The BMS installation would run on the already existing network. UPS: There is a No UPS installed in was observed during the server room. The UPS would have to be incorporated into the building management systemsite visit. Geyser: Not installedThere are two geysers installed on the site that will require connectivity to the BMS. One geyser for each of the buildings. Ground Water Systems: Systems There are no ground water systems on this site. Irrigation Systems There is a sump pump installed for the ground water. This pump would an irrigation system that will require connectivity to a BMS for water flooding monitoring and controlthe BMS. Building 10UNISA XXXXX Campus: This building does not have a BMS installed. The following equipment is installed: Mains Incomer The building is fed from a pole mounted transformer installed on the main substation located at Building 8boundary of the development. The mains low voltage main circuit breaker is not will require a BMS compatible and would require an upgrade circuit breaker that will be monitored for BMS compatibilityon/off status. HVAC Systems: The HVAC system at This building 10 consists mainly of is fitted with YORK split units installed in (manufacturer) that will require connectivity to the offices known as (window shakers). These are mostly manufactured by Mitsubishi. They would require an upgrade for BMS connectivity. A heat pump was also observed during the site assessmentBMS. The HVAC equipment is currently not connected to a BMS system. Lifts: This building does not have a lift installed. Generator: This building There is fed from a 50kVA diesel generator installed on the generator that is located at building 8site complete with a SmartGen Controller. It will be the responsibility of the VBMS contractor during detail design to confirm it has the required modules for BMS connectivity. Lighting The lighting is mostly comprised of fluorescent type of light fittings, both surface and recess mounted. The light fittings would require replacement to have control switchgear that can be connected to a control panel that would be monitored by the BMS. Water Meter: The There is a water pump connected on the site that will require connectivity to the BMS. Currently, the meter is manufactured by Sensus and is fitted with a High Resolution Interface (HRI) pulse and data does not have any sensor monitoring device that can be connected to communicate with a pulse data logger for BMS. There is also a water reservoir tank on the site and the pump will require connectivity to a BMS. The water meter usage is currently being monitored by Zednet Water Monitoring Solutions companyBMS unless the reservoir belongs to the council. Energy Meters: The mains incomer for No energy meters were observed during the building is located at the main substation. The mains incomer is fitted with a Xxxxxxxxx Electrical meter PM3250 which is fitted with a 37 modbus communication protocol. From discussions with personnel on site, it would seem the meters are remotely monitored/connected from the Muckleneuk campussite visit. Water Harvesting: The building has There is a rainwater water harvesting system installed that would in place on the site. The pump will require connectivity a BMS compatible pump controller to a BMSmonitor the pump’s operation.

Appears in 1 contract

Samples: www.unisa.ac.za

Security Systems. The building has a security and access control system installed that would require connectivity to the BMS. This includes CCTV. For access control, Impro seems to be the preferred installer for the access control, systems. Most impro systems can be connected to the bms but remains the responsibility of the contractor to confirm this during detail design and installation. Fire Detection: There is a Fire Detection system installed in the building for the whole site. The main fire panel is a Ziton addressable fire panel that is not connected to a BMS system. Depending on the communication port fitted within the panel, an upgrade maybe required that a BMS interface card be installed for connectivity to the BMS. If the panel already has a TCP/IP port, then no upgrade is required. Server Room: There is a are two server room rooms in this building already connected to a network. The BMS installation would run on the already existing network. There are two UPS: There is ’ installed. A 100kVA and 60kVA UPS that would require connectivity to a UPS BMS. From the site inspection it would seem they are fitted with RS485 ports installed in the server roomfor this functionality. The UPS would have to be incorporated into the building management system. 46 Geyser: Not installed. Ground Water Systems: Not Installed. PV Systems: There is a sump pump PV system installed for the ground watercomprised of 3 x 12kVA inverters. This pump These would require connectivity to a BMS for water flooding monitoring and controlthe BMS. Building 1015: This building does not have a BMS installed. The following equipment is installed: Mains Incomer The building is fed from the main substation located at Building 813. The mains circuit breaker is not BMS compatible and would require an upgrade for BMS compatibility. HVAC Systems: The HVAC system at This building 10 consists mainly of has several split units installed in the offices known as (window shakers). These are mostly manufactured by Mitsubishi. They that would require an upgrade for BMS connectivity. A heat pump was also observed during connectivity to the site assessment. The HVAC equipment is currently not connected to a BMS systemBMS. Lifts: This building does not have a lift Not installed. Generator: This building is not fed from the generator that is located at building 8any standby electricity systems. Lighting The lighting is mostly comprised of fluorescent type of light fittings, both surface and recess mounted. The light fittings would require replacement to have control switchgear that can be connected to a control panel that would be monitored by the BMS. Water Meter: The water meter is manufactured by Sensus and is fitted with a High Resolution Interface (HRI) pulse and data device that can be connected to a pulse data logger for connectivity to a BMS. The water meter usage is currently being monitored by Zednet Water Monitoring Solutions company. Energy Meters: The mains incomer for the building is located at the main substation. The mains incomer is fitted with a Xxxxxxxxx Electrical meter PM3250 PM3255 which is fitted with a 37 modbus communication protocol. The main DB is fitted with an Enermax energy meter that can be connected to a BMS. There are also several PM3255 energy meters installed that monitor usage of the 48 building. The meters are compatible with connectivity to a BMS. From discussions with personnel on site, it would seem the meters are meter is remotely monitored/connected from the Muckleneuk campus. Water Harvesting: The building has a rainwater harvesting system installed that would require connectivity to a BMSNot installed.

Appears in 1 contract

Samples: www.unisa.ac.za

AutoNDA by SimpleDocs

Security Systems. The building has a security and access control system installed that would require connectivity to the BMS. For access control, Impro seems to be the preferred installer for the access control, systems. Most impro systems can be connected to the bms but remains the responsibility of the contractor to confirm this during detail design and installation. Fire Detection: There is a Fire Detection system installed in the building for the whole site. The main fire panel is a Ziton addressable fire panel that is not connected to a BMS system. Depending on the communication port fitted within the panel, an upgrade maybe required that a BMS interface card be installed for connectivity to the BMS. If the panel already has a TCP/IP port, then no upgrade is required. Server Room: There is a server room in this building already connected to a network. The BMS installation would run on the already existing network. UPS: There is a UPS installed in the server room. The UPS would have to be incorporated into the building management system. Geyser: Not installed. Ground Water SystemsSystem: There is a sump pump installed for the ground water. This pump would require connectivity to a BMS for water flooding monitoring and controlNot installed. Building 109: This building does not have a BMS installed. The following equipment is installed: Mains Incomer The building is fed from the main substation located at Building 8. The mains circuit breaker is not BMS compatible and would require an upgrade for BMS compatibility. HVAC Systems: The building has an HVAC system at building 10 consists mainly of split units plant room installed in the offices known as (window shakers)basement. These The plant rooms consists of a chiller plant and pump systems. The chiller plant manufacturer is SCROLL and all the systems have a control unit that can be connected to a BMS system. In the Upper basement there are mostly manufactured by Mitsubishiinverters, heaters, a fan and dampers installed. They The systems installed have a Xxxxxxx control system that would require an upgrade need to be checked for BMS connectivity. A heat pump was also observed during the site assessmentconnectivity to a BMS. The HVAC equipment is currently not connected to a BMS system. Lifts: This building does not have a lift installed. Generator: This building is fed from the generator that is located at building 8. Lighting The lighting is mostly comprised of fluorescent type of light fittings, both surface and recess mounted. The light fittings would require replacement to have control switchgear that can be connected to a control panel that would be monitored by the BMS. Water Meter: The water meter is manufactured by Sensus and is fitted with a High Resolution Interface (HRI) pulse and data device that can be connected to a pulse data logger for connectivity to a BMS. The water meter usage is currently being monitored by Zednet Water Monitoring Solutions company. Energy Meters: The mains incomer for the building is located at the main substation. The mains incomer is fitted with a Xxxxxxxxx Electrical meter PM3250 which is fitted with a 37 modbus communication protocol. From discussions with personnel on site, it would seem the meters are remotely monitored/connected from the Muckleneuk campus. Water Harvesting: The building has a rainwater rain water harvesting system installed that would require connectivity to a BMS.

Appears in 1 contract

Samples: www.unisa.ac.za

Time is Money Join Law Insider Premium to draft better contracts faster.