Common use of Rigid Board Insulation Clause in Contracts

Rigid Board Insulation. 8.3.1 Rigid board insulation shall be cut accurately for the job requirements; all joints will be tightly butted. Insulation shall be cut to fit between standing seams and stiffeners and shall be secured by impaling over metal fasteners or welded pins. The excess pin length will be cut off or bent over. The washer will be set solidly into the insulation surface. All fastener and washer penetrations shall be sealed to provide a complete vapor barrier. Joints at stiffeners, standing seams and angle irons will be insulated and then will be completely sealed.