New Interconnection Customer’s Interconnection Facilities Clause Samples
POPULAR SAMPLE Copied 1 times
New Interconnection Customer’s Interconnection Facilities. As depicted on the one-line diagram in Attachment 3, the new Interconnection Customer’s Interconnection Facilities include: • One (1) three phase, two winding, 4.16/34.5 kV delta-delta step up transformer 7.5/9.375 MVA (ONAN/ONAF), with impedance 7.5%; • One (1) 3 phase, 34.5kV, 200 kV BIL, 600 A, type V2-CA gang operated, vertical break disconnect switch; • Approximately 362 circuit feet of 3-phase, overhead, 34.5 kV, 3/0 Al line from the receiving structure at the New Facility’s substation to Pole 5 of the existing 3-phase, overhead, 34.5 kV, 1/0 Al cable line; o Single channel Direct Transfer Trip (“DTT”) for Existing Facility for tripping breaker 52U1;
New Interconnection Customer’s Interconnection Facilities. As depicted in Attachment 3, the Interconnection Customer’s New Interconnection Facilities consist of: • One (1) three-phase 34500 (Delta) - 4160/2402 V (Wye), 11/13.75 MVA ONAN/ONAF, 200 kV BIL transformer, 9% impedance to replace the existing 7/8.75 MVA transformer
New Interconnection Customer’s Interconnection Facilities. As depicted in Attachment 3, the Interconnection Customer’s New Interconnection Facilities consist of:
1. Connecting Transmission Owner’s Interconnection Facilities
(1) Revenue Meter; One (1) RTU; and 34.5 kV Sub-Transmission generator lead line approximately 4.7 miles in length. No new Connecting Transmission Owner Interconnection Facilities are required for the New Facility.
New Interconnection Customer’s Interconnection Facilities. As depicted on the one-line diagram in Attachment 3, the new Interconnection Customer’s Interconnection Facilities include: • One (1) three phase, two winding, 4.16/34.5 kV delta-delta step up transformer 7.5/9.375 MVA (ONAN/ONAF), with impedance 7.5%; • One (1) 35 kV 1200 A, 200 kV BIL, 25 kA circuit breaker; • Six (6) 36.5 kV MCOV station class lightning arresters; • One (1) 3 phase, 34.5kV, 200 kV BIL, 600 A, type V2-CA gang operated, vertical break disconnect switch; • Approximately 362 circuit feet of 3-phase, overhead, 34.5 kV, 3/0 Al line from the receiving structure at the New Facility’s substation to Pole 5 of the existing 3-phase, overhead, 34.5 kV, 1/0 Al cable line; • System protection devices: o Single channel Direct Transfer Trip (“DTT”) for Existing Facility for tripping breaker 52U1; o Single channel DTT for New Facility for tripping breaker 52U2; and