NEC/Data Forms. Tenant shall perform all electrical work in accordance with NEC and all applicable governmental requirements and in accordance with good engineering practice. All calculations shall conform to the appropriate articles in NEC. Calculation shall include all branch circuits and feeder (service) tabulation. Tenant shall complete and submit for Landlord's approval the forms annexed hereto with respect to Tenant's Service Requirements, Tenant Electrical Data and the Panelboard Schedule. Tenant's estimated maximum demand load 87 shall be based on the summation of (i) 100% of the air conditioning and ventilation load (the greater load of cooling or heating); plus (ii) the percentage of the connected load for kitchen equipment, including refrigerators, freezers. etc., in accordance with Article 220-20 of the NEC; plus (iii) 100% of the connected load for electric water heaters; plus (iv) 100% of connected lighting load (based on lamp wattage for incandescent lamps and watt▇ ▇▇▇ut to the ballast for fluorescent lamps); plus (v) 65% of the connected load of all appliances not mentioned above; plus illuminated signs (based on the equipment connected load set forth on the equipment nameplate); plus receptacles (based on NEC specification).