Furniture Systems. Provide for each grouping of 4 cubicles or less, a wiring assembly consisting of 8 conductors back to the circuit breaker panel, to yield at the systems furnishings 3 hot, 3 neutral. 1 common ground and 1 isolated ground (either three 15‐amp or three 20‐amp breakers.) Power may come through the ceiling, floor or wall but may not exceed the ratio stated above.
Appears in 6 contracts
Samples: www.michigan.gov, www.michigan.gov, www.michigan.gov
Furniture Systems. Provide for each grouping of 4 cubicles or less, a wiring assembly consisting of 8 conductors back to the circuit breaker panel, to yield at the systems furnishings 3 hot, 3 neutral. 1 common ground and 1 isolated ground (either three 15‐amp 15- amp or three 20‐amp 20-amp breakers.) Power may come through the ceiling, floor or wall but may not exceed the ratio stated above.above.