Component Approval Sample Clauses

Component Approval. Only components that were fully tested according to 240-56227516 may be used in an assembly provided that it was also in the assembly when the assembly went for design verification (construction and behaviour). In other words, all components that have protection functionalities must be tested for a conditional short- circuit in the assembly. This means that there shall be a conditional short-circuit test done for each component (CFS) or combination of components (motor starters and series/cascading combinations) in the assembly. The Contractor provides a list of components at tendering stage.