Electrical Tests Sample Clauses

Electrical Tests. The electrical tests apply to qualification of the automatic shut-off valve; they do not apply to qualification of check valves.
AutoNDA by SimpleDocs
Electrical Tests. A total minimum of [***] will be tested. [***].
Electrical Tests a. Perform a contact-resistance test.
Electrical Tests. Upon completion of the factory construction of the unit, the contractor is to carry out tests in accordance with the IEE 17th Edition Regulations. The following tests are to be carried out on site, after the permanent electrical supply has been connected. Particulars: Type of Earthing Prospective Short Circuit Current External Earth Fault Loop Impedance Items: Operation of RCD's Test Results: Maximum Disconnection Time Maximum Earth Fault Loop Impedance Inspection and Completion Certificates are to be issued to the customers authority following testing.
Electrical Tests. X-ray tube current to be measured and if necessary adjusted to ensure that it is within the manufacturer’s tolerances. All operator control panel switches to be tested to ensure correct electrical/mechanical operation, correct tactile fell and tightness. Measure the Digital Video Store (DVS) power supply output voltage and adjust if necessary to be within the manufacturer’s tolerances. Check conveyor relays for correct operation. Check scroll direction and correct if necessary. For the protection of personnel, check for correct operation of all panel interlocks, ensuring that they have not been tampered with or overridden.
Electrical Tests. 1) Tests shall comply with engineered plans and specifications.
Electrical Tests. 44.1 The Customer must ensure the Contractors undertake the electrical tests set out in the Specifications.
AutoNDA by SimpleDocs
Electrical Tests. Insulation resistance measurement at ambient temperature. Sub clause 17.2 - insulation resistance measurement at maximum conductor temperature in normal operation. Sub clause 17.3 - Voltage test for 4 h. Sub clause 17.4.
Electrical Tests. 1. Perform insulation-resistance tests phase-to-phase and phase-to-ground with switch in both source positions.
Electrical Tests. 1. Perform a shield-continuity test on each power cable. Ohmic value shall be recorded.
Time is Money Join Law Insider Premium to draft better contracts faster.